Outback Power Systems vfx 3524m Benutzerhandbuch

Seite von 65
Installation & Programming Manual
                              
FX & VFX Series Inverter/Charger System                     
Copyright 2003  
  OutBack Power Systems, Inc. 
 
 
    
900-0027-1
                                                                19009 62
nd
 Ave NE, Arlington   WA 98223 USA                     
Page 56                                         
Rev 7.2
       08/26/05                                                                    Tel 360 435 6030    Fax 360 435 6019  
MATE SCREENS 
GENERATOR MENU 
The GEN (generator) category of the advanced menu section allows for adjustment of the AC input voltage window and time delays to 
match the characteristics of the AC source if that AC source is a generator.  This setting can be found in the SETUP/FX/INPUT menu.  
All OutBack Power System FX’s other than the “Grid-Tie” FX’s have a default of GEN (generator) as the AC source.  
ADV-----------------
choose product:
FX
MATE
ADV/FX/PAGE1--------
choose category:
ADV
INV
CHGR
PG2
ADV/FX/PAGE2--------
choose category:
PG1
GRID
GEN
PG3
ADV/FX/GEN-------P00
ac input
00.5 min
connect delay
DOWN
INC
DEC
PORT
ADV/FX/GEN-------P00
ac2/gen
108 vac
lower limit
DOWN
INC
DEC
PORT
ADV/FX/GEN-------P00
ac2/gen
140 vac
upper limit
DOWN
INC
DEC
PORT
ADV/FX/GEN-------P00
ac2/gen
30.0 aac
input limit
DOWN
INC
DEC
PORT
ADV/FX/GEN-------P00
ac2/gen
60 cycles
transfer delay
DOWN
INC
DEC
PORT
ADV/FX/GEN-------P00
ac2/gen
OFF
support
DOWN
OFF
ON
PORT
ADV/FX/GEN----------
GEN programming
completed
TOP
ADV
MAIN
Once the password has been correctly entered, the ADV - CHOOSE PRODUCT is displayed.  
Selecting <FX> allows adjustment of the FX’s advanced programming.  
 
  
 
Selecting <PG2> advances the user to the second page of the advanced menu. 
 
 
 
 
Selecting <GEN> allows adjustment of the AC input set points and operation.   
  
 
 
The AC INPUT CONNECT DELAY set point adjusts the time period of when the FX sees an 
acceptable AC source to when it connects the AC loads to that source.  This is useful to allow a 
generator to warm up.  This setting has a range between 0.2 minutes to 15 minutes in 0.1 minute 
increments. 
 
The AC2/GEN LOWER LIMIT set point allows adjustment of the minimum voltage that the AC 
source is allowed to be in order for the FX to connect to that source.  The FX will back off the 
charger if the AC source is at this lower limit.  If the AC source falls below this limit, the FX will 
disconnect from the AC source until it is above this value.  This setting has a range between 70 
vac and 110 vac in 1 vac increments. 
The AC2/GEN UPPER LIMIT set point allows adjustment of the maximum voltage that the AC 
source is allowed to be in order for the FX to connect to that source.  If the AC source exceeds this 
value, the FX will disconnect from the AC source until it is below this value. This setting has a 
range between 130 vac and 150 vac in 1 vac increments. 
The AC2/GEN INPUT LIMIT sets the maximum amount of current the FX allows to be drawn from 
the AC source.  When the AC input current limit is reached, the power draw of the battery charger 
is backed off to prevent overloading the AC source.  If the AC loads exceed this limit, the FX will 
give a warning and start blinking the red “ERROR” LED.  This setting has a range between 5.0 aac 
and 60.0 aac in 1.0 aac increments. 
The AC2/GEN TRANSFER DELAY is the amount of time that the AC input will remain connected 
to the AC source when the AC input voltage drops below the AC2/GEN lower limit setting.  Once 
the AC voltage has risen above the AC2/GEN lower limit setting for the AC INPUT CONNECT 
DELAY time period, the AC source will be reconnected.   This setting has a range between 0 
cycles and 240cycles in 1 cycle increments. 
The AC2/GEN SUPPORT setting is not operational at this time.   
 
 
 
Selecting TOP returns the user to the top of the ADV/FX/GEN menu section.  Selecting ADV 
returns you to the advanced screen to allow selection of another product connected to the MATE.  
Selecting MAIN returns the display to the MAIN screen.