INSTALLATION
• The cap must be 4 feet (1.2 m) horizontally
from any doors, windows, etc.
• The cap must be at least 7 feet (2 m) above
any public walkway.
• The bottom of the cap must be at least 1 foot 
(.3 m) above ground and possibly higher if the
snow accumulation normally exceeds 
1 foot  (.3 m).
• The cap should be positioned such that any
condensate that drips from the cap will not
damage plants, shrubs or onto other
equipment located on the outside of the
restaurant.
Figure 10. Right Angle Adapter Mounting Options.
NOTE: The standard Vent Outlet is shown in Figure 10 exiting from the rear. To adjust the outlet exit to the
right side see the 
COMPONENT-ADJUSTMENT/REPLACEMENT section of this manual.
• The cap should be positioned so that
condensate that drips from the cap will not
allow the water to accumulate on walkways or
other areas, which may freeze and cause an
accident.
• Right angle adapter is provided to minimize
radius of initial bend toward flue piping 
required for tight quarters. See Figure 10 for
direction options.
CAUTION
To avoid FREEZING WATER DAMAGE to the booster heater 
when the outside temperature is below 32°F (0°C) the unit must be
left ON and the venting must be protected from migrating cold air.