272630D Auxiliary Board 
INSTALLATION 
When installing this product... 
1. Read these instructions carefully. Failure to 
follow them could damage the product or 
cause a hazardous condition. 
2. Check ratings given in instructions and on 
the product to ensure the product is suitable 
for your application. 
3. Installer must be a trained, experienced 
service technician. 
4. After installation in complete, check out 
product operation as provided in these 
instructions. 
CAUTION: 
1. Disconnect power supply before beginning 
installation to prevent electric shock and 
equipment damage. 
2. All wiring must comply with applicable local 
electrical codes, ordinances and regulations. 
3. DO NOT electrically operate the ML6-7984 
actuator before assembly to the valve 
because damage not apparent to the installer 
may occur. Mount the actuator to the valve 
before connecting to power. 
Assembly 
1. Remove plastic cover from the ML6-7984 
by loosening the two screws located on the 
top. (Note: These screws are captive. 
Rotate three complete revolutions to 
remove cover). 
2. Slide the auxiliary board into the two slots 
at the bottom of the bridge. Push back and 
snap the board into the fingers. (See Fig. 1) 
3. Connect one end of the 4-pin connector to 
the main board and the other end to the 
auxiliary board if it is not already connected. 
The connectors are keyed and only install 
one way. 
4. Mount the actuator onto the valve body and 
connect wiring. 
5. Reinstall cover after operational check. 
Fingers  
Bridge 
Slots 
1. Install 
circuit 
board 
Fig. 1 - Installation of auxiliary board 
OPERATION 
The first time the valve is powered, the 
microprocessor will automatically cycle the 
valve through a full stoke to calibrate its 
position. Any stroke between 1/2" (13 mm) and 
1" (25 mm) will be divided into 30 equal steps. 
Run time will be proportional to stroke length. 
(For example: nominal timing for 3/4" stroke 
is 63 seconds. For 1/2" stroke this would be 
42 seconds). The LED lights up when 
terminals T5-T6 are powered, and flash when 
the actuator is in motion. 
NOTE: 272630D requires that the actuator be 
continuously powered, so ML6984 must be 
wired in "5-wire" configuration. 
C-NC contact  C-NO contact 
CLOSED 
CLOSED 
2-10 V, 
when valve 
when valve 
(4-20 mA 
position is 
position is 
into 
below trim pot  above trim pot  500 
Ω
setting (direct  setting (direct 
feedback 
acting). 
acting). 
output  COM 
Trim pot 
J1
LED 
+FB
NC 
C  NO 
RLY1 
-COM 
Connect to main 
board for position 
feedback. 
Fig. 2 - Wiring and operation of auxiliary 
board 272630D