Honeywell GES Benutzerhandbuch

Seite von 3
DN-6872 • 12/19/02  —  Page 3 of 3
GE Series Wiring with AVS44 Sync Module
GEC Models
Conventional
Wiring
GEH/GES Models
Conventional
Wiring
6872wirc2.wmf
6872wirc1.wmf
6872wirs.wmf
 
Horn Ratings over Input Voltage Range of 16 – 33 V
Horn Mode
dBA @ 10' (3.048 m)
per UL 464
HIGH dB
dBA @ 10' (3.048 m)
per UL 464
LOW dB
DC (mA)
FWR (mA)
16 V
24 V
33 V
16 V
24 V
33 V
16 V
24 V
33 V
16 V
24 V
33 V
 Temporal 3 2400 Hz
  78
  83
  84
  71*
  75
  77
13
19
24
27
37
43
 Temporal 3 Mechanical
  76
  81
  82
  70*
  73*
  76
11
16
22
23
33
40
 Temporal 3 Chime
  70*
  71*
  71*
  66*
  68*
  70*
9
12
15
19
24
29
 Continuous 2400 Hz
  81
  86
  87
  74*
  78
  80
14
21
28
21
42
48
 Continuous Mechanical
  80
  84
  85
  72*
  76
  78
13
18
25
27
37
44
 Continuous Chime
  70*
  71*
  73*
  66*
  68*
  70*
10
12
15
19
24
30
 Whoop
  82
  83
  83
  69*
  72*
  75
43
51
56
51
58
62
6872horn.tbl
TABLE NOTES: 1) *Operating the horn in this mode at this voltage will not meet the minimum UL reverberant sound level
required for public mode fire protective service. These settings are acceptable only for private mode fire alarm use. Use the high
dBA setting for public mode application (not applicable when using the chime tone — the chime tone is always private mode).
2) The sound output for the temporal 3 tone is rated lower, as the time the horn is off is averaged into the sound output rating.
While the horn is producing a tone in the temporal 3 mode, its sound pressure is the same as when in continuous mode.