Crestron electronic CLS-EXP-DIMFLV Benutzerhandbuch

Seite von 8
 
CLS-EXP-DIMFLV 
Crestron Electronics, Inc.
 
Installation Guide – DOC. 6680A
 
15 Volvo Drive   Rockleigh, NJ 07647
 
(2020652)
   
Functional Summary 
The CLS-EXP-DIMFLV enables the expansion of the 
Crestron
®
 iLux™ Integrated Lighting System and other 
Crestron lighting dimmers to support 120 - 277 Volt loads 
up to 16 Amps. It allows any output channel of a 
compatible dimmer or switch to control a fully loaded 
circuit of 0-10 VDC fluorescent ballasts
1
, non-dimmed 
lighting (incandescent, HID, magnetic low voltage 
(MLV), electronic low voltage (ELV), neon/cold cathode, 
and fluorescent ballast) up to 16 amps, and motors rated 
up to 1/2 HP @ 120 Volts, 1 HP @ 230/277 Volts.  
The CLS-EXP-DIMFLV is designed for mounting to a 
vertical surface. Conduit knockouts are provided on the 
bottom and lower sides. All connections are made via 
screw terminals behind the front cover. 
•  Works with Crestron iLux (CLS(I)-C6),  
CLW-Series dimmers
2,3
, CLX-Series dimmers
3
and DIN-1DIMU4
3
 
•  Emulates the characteristics of the dimmer that is 
controlling it  
•  Up to five Expansion Modules can be connected 
to a single iLux dimmer channel  
•  Supports 0-10 VDC fluorescent, non-dimmed 
lighting (including HID), and motors rated up to 1 
HP 
•  Built-in air gap relay at the output 
1. 
Ballasts must comply with the specifications for control by DC 
voltage in ANSI C82.11:2002 and IEC60929:2006. 
2. 
CLW-Series devices must have a dedicated neutral. 
3. 
The CLS-EXP-DIMFLV can only be controlled by forward-phase 
dimmer modules. It is not compatible with the CLX(I)-1DELV4. If 
connected to a DIN-1DIMU4, the DIN-1DIMU4 must be set to 
operate as a forward-phase dimmer or a non-dimming switch. 
CLS-EXP-DIMFLV Physical View 
 
Specifications 
CLS-EXP-DIMFLV Specifications 
SPECIFICATION DETAILS 
Load Ratings 
 Output 
Channels 
 Load 
Ratings: 
   Lamp 
 
 
   Motor 
 
 Minimum 
Load 
    at 120 Volts 
    at 230 Volts 
    at 277 Volts 
 Load 
Types 
 
 
16 Amps @ 120 – 277 Volts 
(70 mA max current sink for 0-10 
VDC ballasts) 
1/2 HP @ 120 Volts,  
1 HP @ 230/277 Volts 
 
15 Watts 
25 Watts 
30 Watts 
Dimmable Loads 
0-10 VDC dimmable fluorescent 
ballasts (i.e. Advance Mark 7 or 
other ballasts that are compliant 
with the specifications for control 
by DC voltage in ANSI 
C82.11:2002 and IEC60929:2006) 
Non-Dim Loads 
Incandescent, HID, magnetic low 
voltage (MLV), electronic low 
voltage (ELV), neon/cold cathode, 
and fluorescent ballasts  
Motors 
Up to 1 HP @ 230/277 Volts 
Input Voltages 
 Line 
Power 
 Control 
Input 
 
120 to 277 Volts AC, 50/60 Hz 
120 or 230 Volts AC, 50/60 Hz, 
phase independent of line power 
and load, presents 25 Watts load 
to the controlling device 
Electrical Terminals 
Captive screw type; 
Accommodates two 22-12 AWG 
(0.34-4.0 mm
2
) wires 
Enclosure 
Surface mount module with (2) 
integral mounting flanges, 
galvanized steel w/gray matte 
powder coat front panel, extruded 
aluminum heat sink, 1/2” and 3/4” 
conduit knockouts provided on 
bottom and lower left & right sides 
Environmental 
 Temperature 
 Humidity 
 Maximum 
Heat 
Dissipation 
 
32° to 104°F (0° to 40°C) 
10% to 90% RH (non-condensing) 
68 BTU/Hr 
Dimensions 
 Height 
 Width 
 Depth 
 Weight 
 
8.82 in (22.40 cm) 
6.39 in (16.23 cm) 
3.18 in (8.08 cm) 
3.3 lbs (1.5 kg) 