Conair MPA Benutzerhandbuch

Seite von 86
S
PECIFICATIONS
: MPW (W
ATER COOLED
)
microKool Portable Chillers
UGH004/0999
2-6
D
ESCRIPTION
MODEL
MPW-1.5
MPW-2
MPW-3
MPW-4
MPW-5
MPW-7.5
MPW-10
Performance characteristics
Capacity  {tons} *
1.4
1.8
3.1
4.1
4.8
7.6
10.2
Compressor  Hp {kW}
1.5 {1.12}
2 {1.49}
3 {2.24}
4 {2.98}
5 {3.73}
7.5 {5.59}
10 {7.45}
Pump Hp  {kW} †
0.33 {0.246}
0.50 {0.373}
0.75 {0.559}
1.5 {1.12}
1.5 {1.12}
1.5 {1.12}
1.5 {1.12}
Chilled water flow   gpm {l/min} ‡
3.4 {12.9}
4.5 {17.0}
7.5 {28.3}
9.9 {37.5}
11.4 {43.2}
18.2 {68.9}
24.5 {81.0}
Chilled water pressure  psi {bar} §
20 {1.4}
26 {1.8}
34 {2.3}
38 {2.6}
38 {2.6}
37.5 {2.6}
37 {2.5}
Reservoir capacity  gal (l)
10 {37.9}
10 {37.9}
10 {37.9}
30 {114}
30 {114}
30 {114}
30 {114}
Condenser water flow   gpm {l/min}
4.3 {16.3}
5.6 {21.2}
9.4 {35.6}
12.4 {47.0}
14.3 {54.2}
22.8 {86.4}
30.6 {116.0}
Dimensions inches {mm}
A - Height  **
45 {1143}
45 {1143}
45 {1143}
56 {1422}
56 {1422}
70 {1778}
70 {1778}
B - Depth
32 (812}
32 {812}
32 {812} 
48 {812}
48 {812}
48 {812}
48 {812}
C - Width
29 {737}
29 {737}
29 {737}
34 {737}
34 {737}
34 {737}
34 {737}
Weight lb {kg}
Shipping weight 
550 {249}
755 {342}
755 {342}
1010 {458}
1010 {458}
1250 {567}
1250 {567}
Installed weight
420 {190}
585 {265}
585 {265}
840 {381}
840 {381}
1080 {490}
1080 {490}
Utility requirements
Water connections  NPT (female) inches
1
1
1
1.5
1.5
1.5
1.5
Process and condenser water      inches
1
1
1
1.5
1.5
1.5
1.5
Voltages  running and full load amps
run
full
run
full
run
full
run
full
run
full 
run
full
run
full
208V/3 phase/60hz                                    8.8
15.5     13.7
15.9
17.7
22.3
23.9
28.3
27.0
30.5
34.9
41.5
44.2
50.8 
230V/3 phase/60hz                                 
8.0
14.0    12.4
14.4
16.0
20.2
21.6
25.6
24.4
27.6
31.6
37.6
40.0
46.0
460V/3 phase/60hz
4.0
7.0
6.2
7.2
8.0
10.1
10.8
12.8
12.2
13.8
15.8
18.8
20.0
23.0
575V/3 phase/60hz
3.2
5.6
5.0
5.8
6.4
8.1
8.6
10.2
9.8
11.0
12.6
15.0
16.0
18.4
Flow  Rate (gpm)
Pressure  (psi)
SPECIFICATION NOTES
*  Based on 50° F (10° C) water temperature (100% water) leaving the chiller, standard pump selections, 85° F (27° C) condenser water supply
@ 25 psi minimum. Consult factory for other conditions.
† Standard pump selection. Larger pumps available as options. 
‡  Based on 50° F water temperature leaving the chiller and 60° F (15° C) water temperature returning to the chiller.
§ Pressure at pump discharge.
** Control can be extended upward approximately 11 inches, which may or may not increase the overall height of the unit.
Specifications may change without notice. Check with a Conair representative for the most current information.
60 HZ PUMP PERFORMANCE CURVES