PLANNING
GUIDE
EERV3015, ERV3615
Renaissance
  
30”, 36” Wide,  
High Extension Slim Raised Vents
Document # PG08-004
Revised 10/28/11   Page 2/3
Duct work Design Tips
 
Wherever possible, reduce the number of transitions and turns to as 
few sharp angles as possible. Two staggered 45° angles are better 
than one 90°. Keep turns as far away from the hood exhaust as 
possible, with as much space between each bend as possible.
 
For best performance, use round duct instead of rectangular when 
possible, especially when elbows are required.
 
If multiple elbows are used, try to keep a minimum of 24” of straight 
duct between them. Avoid “S” or “back to back” configurations of 
adjacent elbows.
 
Do not use flexible metal duct.
Calculating the Maximum Duct run Length
 
Do not use duct work that is smaller in cross-sectional area than the 
required duct sizes in the table to the right.
 
For best performance, keep the duct run as short as possible and 
never exceed the maximums stated at the right.
 
The maximum straight duct length for the raised vent system depends 
on the model of remote or in-line blower used with the vent system 
and the number of elbows and transitions used. The Equivalent 
Number of Feet for each elbow and transition (see table) must be 
subtracted from the maximum straight length to compensate for 
wind resistance. To determine the maximum allowable length of the 
duct work, subtract all of the equivalent lengths of the elbows and 
transitions from the Blower Maximum Duct Straight Length.
For example, for a raised vent system using 3 ¼” X 10” rectangular 
duct, two (2) 3 ¼” X 10” 90° elbows, a 3 ¼” X 10” rectangular to 10” 
round transition, and a rEMP16 remote blower:
 
From the Blower Maximum Duct Straight Length table, the 
maximum length without transitions and elbows is 60 feet.
 
The equivalent length of each 90
° elbow is 15 feet.
 
The equivalent length of 45
° elbow is 2 feet.
 
The equivalent length of the transition is 4 feet.
 
The total equivalent length of the above components is: 15 feet + 15 
feet + 4 feet + 2 feet = 36 feet.
 
The maximum amount of straight duct that can be used with a 
REMP16 and the above components is: 60 feet - 34 feet = 24 feet.
Equivalent number of Feet - 
Duct Elbows and Transitions
45° elbow 
8 Inch
3 feet
3 ¼” X 10 
45° elbow
7 feet
45° elbow
10 Inch
2 feet
3 ¼” X 10 
90° elbow
15 feet
90° elbow 
8 Inch
7 feet
3 ¼” X 10 
90° flat elbow
20 feet
90° elbow
10 Inch”
5 feet
3 ¼” X 10  
to 8” round
transition
4 feet
90° 3 ¼” X 10 to 8” 
round
transition
25 feet
3 ¼” X 10  
to 10” round
transition
4 feet
Roof cap
*
Wall cap
*
* The equivalent lengths of roof and wall caps vary with model and 
configuration. For equivalent length, contact the manufacturer or a qualified 
HVAC specialist.
raised Vent 
Model no.
approved Dacor 
Blowers* 
ERV3015
 
ERV3615
Remote blowers: 
REMP3 or REMP16
In-line blowers: 
ILHSF8 or ILHSF10
*For detailed information on the remote/in-line blowers,  
refer to the blower installation instructions.
Duct Size 
Used
Blower Maximum Duct Straight Length
rEMP3 remote Blower
rEMP16 remote Blower
iLHSF8 in-line Blower
iLHSF10 in-line Blower
8 inch
50 feet (15.2 meters)
60 feet (18.3 meters)
50 feet (15.2 meters)
60 feet (18.3 meters)
10 inch
40 feet (12.2 meters)
70 feet (21.3 meters)
40 feet (12.2 meters)
70 feet (21.3 meters)
3 ¼” X 10”
40 feet (12.2 meters)
60 feet (18.3 meters)
40 feet (12.2 meters)
60 feet (18.3 meters)