Panasonic CZCSWKC2 Bedienungsanleitung
4-7-2-2-3.
Fan speed switch
When any button is clicked, the selected button remains depressed.
When any other Fan speed button is clicked on, the previously selected
button reverts to its non-depressed state.
Auto fan speed cannot be selected in fan operation.
* For some indoor unit models, it may be impossible to select “Auto” (Auto
When any other Fan speed button is clicked on, the previously selected
button reverts to its non-depressed state.
Auto fan speed cannot be selected in fan operation.
* For some indoor unit models, it may be impossible to select “Auto” (Auto
fan speed).
4-7-2-2-4.
Swing/Flap
When any button is clicked, the selected button remains depressed.
When any other Flap button is clicked on, the previously selected button
reverts to its non-depressed state.
* Some flap settings are unavailable, depending on the selected operation
When any other Flap button is clicked on, the previously selected button
reverts to its non-depressed state.
* Some flap settings are unavailable, depending on the selected operation
mode.
4-7-2-2-5.
Prohibition switch
When any button is clicked, the selected button remains depressed.
When any other prohibition mode button is clicked on, the previously selected
button reverts to its non-depressed state.
Only those set under prohibition settings can be used.
When any other prohibition mode button is clicked on, the previously selected
button reverts to its non-depressed state.
Only those set under prohibition settings can be used.
R/C OK :Operation with the remote control unit is OK.
Prhbt 1 :The remote control unit cannot be used for switching On/Off.
Prhbt 2 :The remote control unit cannot be used for switching On/Off,
Prhbt 1 :The remote control unit cannot be used for switching On/Off.
Prhbt 2 :The remote control unit cannot be used for switching On/Off,
temperature setting and operation mode switching.
Prhbt 3 :The remote control unit cannot be used for temperature setting
and operation mode switching.
Prhbt 4 :The remote control unit cannot be used for operation mode
switching.
Prhbt 5 :The remote control unit cannot be used for switching On/Off.
Prhbt 6 :The remote control unit cannot be used for switching On/Off,
Prhbt 6 :The remote control unit cannot be used for switching On/Off,
temperature setting and operation mode switching.
Prhbt 7 :The remote control unit cannot be used for temperature setting
and operation mode switching.
* The functions for Prhbt 1–4 can be changed using the “Maintenance” – “R/C
prohibition settings”.
* Prohibit 1–4 are for the CZ-CFUNC2.
4-7-2-2-6.
Temperature setting
Click on the up and down buttons in the center right of the Remote Control screen
to raise or lower the temperature displayed in the set temperature column.
to raise or lower the temperature displayed in the set temperature column.
Heat
:16 - 26°C
Dry/Cool :18 - 30°C
is the available setting range. Temperature cannot be set in fan operation.
* Temperature setting ranges differ between indoor unit models.
is the available setting range. Temperature cannot be set in fan operation.
* Temperature setting ranges differ between indoor unit models.
* Temperature setting ranges can be changed using “Maintenance” – “Register
I/D unit high/low-limit temperature”.