Panasonic CZCSWKC2 Bedienungsanleitung

Seite von 104
4-25.  Register I/D unit upper/low-limit temperature
[Procedure]
  On the menu bar, select “Maintenance” – “Register I/D unit high/low-limit 
temperature”. 
(Password level 2)
Set upper and lower limit temperatures to restrict the set temperatures of indoor units.
 
  :Use to clear all and select all.
 
  :Use to select floor areas.
    :Use to select the display order.
 
  :Register settings.
 
  :Revert to the previously registered state.
 
 
: Select the upper limit temperature/lower limit   
temperature.
 
  :Set enabled/disabled.
 
  : Apply the set values of upper limit temperature/lower 
limit temperature. Or, apply the enabled/disabled 
settings.
Key
· Select 
   
 
: Selects the indoor unit to control. 
Click to add a check mark.
· Address     
 
:Displays the address numbers of indoor units.
· Name 
   
 
:Displays the names of the indoor units.
· Valid 
   
 
:Sets enabled/disabled.
· High limit temperature  :Displays the upper limit temperatures of indoor units.
· Low-limit temperature 
:Displays the lower limit temperatures of indoor units.
Select/clear all
Floor area
Sort display
Register/cancel 
setting data
Set upper/
lower limit 
temperatures
Setting  
enable/disable