Hirschmann OZD Modbus Plus G12-1300 Fiber Interface Техническое Руководство

Seite von 2
 
Hirschmann Automation and Control GmbH  
www.beldensolutions.com
 
05-08-2014
Page 1 of 2
 
Product information
OZD Modbus Plus G12-1300
Fiber Interfaces:Fieldbus Repeater:Modbus Plus LWL-Repeater:OZD Modbus Plus G12-1300
Name
OZD Modbus Plus G12-1300
 
interface converter electrical/optical for Modbus Plus-field bus networks; repeater function; for quartz glass FO; long-haul version
Delivery informations
Availability
available
Product description
Description
interface converter electrical/optical for Modbus Plus-field bus networks;
repeater function; for quartz glass FO; long-haul version
Port type and quantity
2 x optical: 4 sockets BFOC 2.5 (STR); 1 x electrical: Sub-D 9-pin, female, pin assignment according to Modbus Plus-Standard
Type
OZD Modbus Plus G12-1300
Order No.
943 821-021
Electrical interface
Signal type
Modbus Plus
Bit rate
1 Mbit/s
Signal delay time (optional input/output)
<1 µs
Input/output signal
Modbus Plus Bus
Length of Modbus cable
100 m
Connection capability
max. 31 terminal devices
Terminator
external
Galvanic isolation
shielding/housing: no; data lines/housing: yes
Optical interface
Wavelength
1310 nm
Cascadibility
not limited
More Interfaces
Power supply
5-pin terminal block, screw mounting
Signaling contact
5-pin terminal block, screw mounting
Network size - length of cable
Single mode fiber (SM) 9/125 µm
8000 m
8 dB link budget at 1310 nm; A = 0.5 dB/km, 2 dB reserve
Multimode fiber (MM) 50/125 µm
7000 m
10 dB link budget at 1310 nm; A = 1 dB/km, 3 dB reserve
Multimode fiber (MM) 62.5/125 µm
7000 m
10 dB link budget at 1310 nm; A = 1 dB/km, 3 dB reserve
Multimode fiber HCS (MM) 200/230 µm
-
Power requirements
Operating voltage
24 VDC -20% ... 48 VDC +10% non-interchangeable, safety extra-low voltage
Current consumption
120 mA at +24 VDC; 65 mA at + 48 VDC
Power consumption
3.1 W
Redundancy
Redundancy functions
HIPER-Ring (ring structure), redundant 24 V infeed
Ambient conditions
Operating temperature
0 ºC to +60 ºC
Storage/transport temperature
-40 ºC to +70 ºC
Relative humidity
<95% (non-condensing)
Mechanical construction
Dimensions (W x H x D)
40 x 111 x 73.5 mm
Mounting
DIN rail or mounting plate