Panamax MB1000 Benutzeranleitung

Seite von 17
11
RS-232 Communications Protocol & Command Set
RESET FACTORY SETTINGS
Resets all of the custom configuration settings 
Send to UPS: 
 
!RESET_ALL<CR>
Action:   
 
Sets all state variables to the default 
values
Response from UPS: 
$FACTORY SETTINGS  
 
   RESTORED 
<CR>
_________________________________________
QUERIES
IDENTIFY
Request that the unit identify itself.
Send Query to UPS: 
?ID<CR>
Action:    
 
Model number and firmware revision 
will be provided.
Response:   $PANAMAX<CR>
 
 
 
$MB1000<CR>
   $FIRMWARE 
revision<CR>
_________________________________________
OUTLET STATUS
Requests the on/off status of the outlet banks
Send Query to UPS: 
?OUTLETSTAT<CR>
 
 
 
status = {ON, OFF}
Action:    
 
On/Off status for outlets 
 
   will 
be 
provided.
Response:   $BANK1 
status<CR>
   $BANK2 
status<CR>
_________________________________________
POWER STATUS
Requests the status of the input voltage.  The responses are the 
same as Power Fault Status Change.
Send Query to UPS: 
?POWERSTAT<CR>
Action:   
 
Power status messages will be  
   returned
Response: 
 
Normal operation  $PWR = 
NORMAL<CR>
Overvoltage 
 
$PWR = OVERVOLTAGE<CR>
Undervoltage 
 
$PWR = UNDERVOLTAGE<CR>
Lost Power 
 
$PWR = LOST POWER<CR>
Test Mode 
 
$PWR = TEST<CR>
_________________________________________
VOLTAGE
Requests the input and output voltages
Send Query to UPS: 
?POWER<CR>
Action:   
 
Voltage status messages will be  
   displayed
 
 
Response: 
 
$VOLTS_IN = vvv<CR>
 
 
 
$VOLTS_OUT = vvv<CR>
 
 
 
$WATTS = xxxx<CR>
 
 
 
$VA = xxxx<CR>
xxx is expressed in decimal format.  If the value is less than 100, 
the hundreds digit is represented with a 0.  For example a line 
voltage of 92VAC would be expressed as: $VOLTAGE =092
_________________________________________
LOAD LEVEL STATUS
Requests the load level, expressed as percentage of maximum.
Send Query to UPS: 
?LOADSTAT<CR>
Action:   
 
Load level will be displayed
Response: 
 
$LOAD = xxx<CR>
xxx is the load level (percentage of maximum load) expressed in 
decimal format.  If the value is less than 100, the hundreds digit 
is represented with a 0. 