Cycle Times
• 
Press the UP
  
„ 
or DOWN
  
‰ 
arrow to scroll to menu item
• 
Press the CHECKMARK
   
key to select a menu item
•  Press the 
UP
   
„ 
or 
DOWN
  
   
arrow to change a selection
• 
Press the CHECKMARK
   
key to save your selection
Default Values are shown for each selection
Scroll to ADV SETUP and select
Select CYCLE TIMES
Select either USE DEFAULTS or CUSTOM. When USE DEFAULTS is selected, the pro-
gram calculates the cycle times based on hardness and resin volume. When CUSTOM is 
selected, you can set custom cycle times.
Use this setting to adjust the number of minutes for backwash. You generally will not 
need to change this setting.
For commercial applications, this value can normally be set to 60 minutes. It can be 
extended if you find the brine is not being rinsed out properly within this time.
This value is calculated for household units. For commercial units, you should adjust this 
value to 10 minutes, but it is not required.
This will only show if you have selected a 5-cycle valve. This is the refill time. This value 
can be found in the unit’s installation manual. For example, if you have a Hi-Flo 22 WS-
90 water softener (3 ft³) and you want to set a capacity of 60,000 grains, then using 
the chart in Appendix A of the Hi-Flo 22 manual show a time setting of 12 minutes.
For a 4-cycle valve, the refill is controlled by AUX OUTPUT 2 and the refill time is set 
there. See page 46.
This concludes the Cycle Times section. Continue to press the X key to return to the Main Menu.
 > 5) Adv Setup
system ok
7:32 am 2-1-08
 > 3) cycle times
cycle times
>use defaults
backwash time
10 minutes
brine draw-rinse
71 minutes
fast rinse
7 minutes
Customizing the Setup
 
Custom­izing the Setup 
32
 31
  CULLIGAN GLOBAL ELECTRONIC CONTROLLER
fill Time
7 minutes