Confidential and Proprietary Information of ZTE CORPORATION
The weight bearing capacity of the equipment room ground should be
1,200 kg/m
2.
Power Supply of Equipment
Voltage
Nominal working voltage: -48 VDC
Range: -57 VDC ~ -40 VDC
Power Consumption
The maximal power consumption of each module is as follows:
TRM: 160 W
TRM: 175 W
CMM: 16 W
Fan: 60 W
CDU or RDU: 5 W
The power consumption of the integrated equipment in full configuration is
less than 2,200 W.
less than 2,200 W.
Heat in the rack is from the TRM and AEM in the carrier plug-in shelf.
The heat consumption distribution of each module:
TRM: 120 W
ETRM: 135 W
AEM: 45 W
CMM (two): 20 W
Fan and other parts: 30 W
Under full configuration:
Without ETRM, the heat consumption of each carrier shelf, 600 W;
integrated equipment, less than 2,200 W
With ETRM, the heat consumption of each carrier shelf (fan included),
600 W; integrated equipment, less than 2,350 W