ZTE Corporation ZXG-BTS2 Benutzerhandbuch

Seite von 139
 
ZXG10-BTS (V2.9) Technical Manual 
20 
Confidential and Proprietary Information of ZTE CORPORATION  
The weight bearing capacity of the equipment room ground should be 
1,200 kg/m
2.
 
Power Supply of Equipment 
Voltage 
Nominal working voltage: -48 VDC 
Range: -57 VDC ~ -40 VDC 
Power Consumption 
The maximal power consumption of each module is as follows:  
TRM: 160 W 
TRM: 175 W 
CMM: 16 W 
Fan: 60 W 
CDU or RDU: 5 W 
The power consumption of the integrated equipment in full configuration is 
less than 2,200 W. 
Heat in the rack is from the TRM and AEM in the carrier plug-in shelf. 
The heat consumption distribution of each module:  
TRM: 120 W 
ETRM: 135 W 
AEM: 45 W 
CMM (two): 20 W 
Fan and other parts: 30 W 
Under full configuration:  
 
Without ETRM, the heat consumption of each carrier shelf, 600 W; 
integrated equipment, less than 2,200 W 
 
With ETRM, the heat consumption of each carrier shelf (fan included), 
600 W; integrated equipment, less than 2,350 W