SALCOM 12-03-0000 POCSAG RECEIVER with RELAY OUTPUTS
Issue 06/02
Sea Air and Land Communications Ltd
Page 4
COMMANDS
The OUTPUT Relays of the 12-03-0000 are controlled by a series of
numeric commands sent in the form of a numeric or alphanumeric pager
message.
Note: For best sensitivity and range, it is better to send the command
as a numeric paging message, as this uses the least number of
characters.
Command Format:   
UUx..x0y..y9
UU
Unit number
This must be entered as 2 digits 00 - 99
N.B. 00 is a group call and all 12-03-0000 units with the same
RIC will receive the command.
x
Relay to go ON.
Each digit corresponds to the matching relay number. Any
combination of Digits 1-8 can be entered in any order. If none
are entered then  the function has no effect.
0
End entry of Output ON values
This terminates the list of outputs to turn on. This character in
mandatory.
y
Relay to go OFF.
Each digit entered corresponds to the matching relay number.
Any combination of Digits 1-8 can be entered in any order. If
none are entered then  the function has no effect.
9
End entry of Outputs OFF values & Ignore rest of entry.
This terminates the list of outputs to turn OFF and Informs the
12-03-0000 to ignore the rest of the message. This allows a
text message to follow the command.
Examples
To control relays using the TELECOM Paging Network
Message:
026PPPPPPPP UUx..x0x..x9
|     |
         |
|     |
         12-03-0000 Command
|     | the pager number[TELECOM PAGER No]
| the network access number
To control relays using a SALCOM 1131
Message:
NN[MESSAGE]UUx..x0x..x9
|     | 
           |
|     |
           | 12-03-0000 Command
|     | the message button
| The quick dial number