ademco 201503 Benutzerhandbuch
Honeywell Internal
PC-503 User Manual
Overview
PC-503 is a commissioning tool designed to work with INNTOOL/EngINN application. PC-503 comes with a USB to Mini
USB cable. USB cable provides power and communication interface to a laptop or personal computer. The device has
two LEDs which blinks to show transmit (Tx) and receive (Rx) communication with laptop.
USB cable. USB cable provides power and communication interface to a laptop or personal computer. The device has
two LEDs which blinks to show transmit (Tx) and receive (Rx) communication with laptop.
Important Note: PC-503 will not work with the INNCOM SNEEZER or any other INNCOM legacy tool. PC-503 is an RF-only
device and does not provide either S5 or IR5 interface.
device and does not provide either S5 or IR5 interface.
Specification:
Parameter
Parameter
PC503
RF Data Rate
250kbps
Antenna Type
SMT
Indoor Range
70ft
Transmit Power
3mW (+5dBm)
Receive Sensitivity
-95dBm
Frequency Band
2.4Ghz
Encryption
AES-128
Protocol
802.15.4
Frequency Channels
11-26
Input Voltage
5VDC (USB)
Operating Ambient Temperature
0°C–40 °C
LEDS
Flashes to show Transmit and Receive RF
Frames.