Honeywell International Inc. AZWDGL Benutzerhandbuch
Installation and Operations Guide
|
Adding Alerton Wireless Temperature Sensors
© Honeywell
LTBT-TM-AZWIOG
Rev. 0001BETA
19
Adding Alerton Wireless Temperature Sensors
The Alerton Wireless Temperature Sensor (WTS) integrates with the AZW-5000
to add programmable space temperature control without the expense of cutting
walls and running wires. The WTS is available in two models: one with a
temperature adjustment knob and manual override, and one without.
to add programmable space temperature control without the expense of cutting
walls and running wires. The WTS is available in two models: one with a
temperature adjustment knob and manual override, and one without.
A WTS differs from other devices you might add to an AZW-5000 network
because it does not need to be wired to a transceiver. It has an internal radio that
acts as its transceiver.
because it does not need to be wired to a transceiver. It has an internal radio that
acts as its transceiver.
You can pair a WTS with an AZW-5000 transceiver or repeater, but not with a
coordinator.
coordinator.
To pair a WTS with an AZW-5000
1.
Set up the WTS using the WTS Installation Instructions
(LTBT-TM-WTS-INST-USA).
(LTBT-TM-WTS-INST-USA).
2.
Set the WTS DIP switches labeled S2 and S3 to match the ZigBee MAC
address DIP switches on the associated AZW-5000.
address DIP switches on the associated AZW-5000.
WTS AVs and BVs
When a WTS device is connected to the network, the associated AZW-5000
reads its AVs and returns the values shown.
reads its AVs and returns the values shown.
N o t e
Setpoint Adjust Range is set using AV-25 in the AZW-5000.
You can change the
AZW-5000 points to which the values are written by setting
these AZW-5000 AVs:
• AV-84 specifies where the temperature sensor reading is written
• AV-85 specifies where the temperature setpoint is written
• AV-86 specifies where the occupancy override status is written
• AV-87 specifies where the battery status is written
Function
WTS Point
Default AZW-5000 Point
Temperature sensor reading
AV-80
AV-50
Temperature setpoint
AV-81
AV-51
Occupancy override status
AV-82
BV-52
Battery status
AV-83
BV-53