Honeywell International Inc. AZWDGL Benutzerhandbuch

Seite von 30
 Installation and Operations Guide 
Adding Alerton Wireless Temperature Sensors
 © Honeywell 
LTBT-TM-AZWIOG
Rev. 0001BETA
  
19
 
Adding Alerton Wireless Temperature Sensors
The Alerton Wireless Temperature Sensor (WTS) integrates with the AZW-5000 
to add programmable space temperature control without the expense of cutting 
walls and running wires. The WTS is available in two models: one with a 
temperature adjustment knob and manual override, and one without.
A WTS differs from other devices you might add to an AZW-5000 network 
because it does not need to be wired to a transceiver. It has an internal radio that 
acts as its transceiver. 
You can pair a WTS with an AZW-5000 transceiver or repeater, but not with a 
coordinator.
To pair a WTS with an AZW-5000
1.
Set up the WTS using the WTS Installation Instructions 
(LTBT-TM-WTS-INST-USA).
2.
Set the WTS DIP switches labeled S2 and S3 to match the ZigBee MAC 
address DIP switches on the associated AZW-5000.
WTS AVs and BVs
When a WTS device is connected to the network, the associated AZW-5000 
reads its AVs and returns the values shown.
N o t e
Setpoint Adjust Range is set using AV-25 in the AZW-5000.
You can change the 
AZW-5000 points to which the values are written by setting 
these AZW-5000 AVs:
• AV-84 specifies where the temperature sensor reading is written
• AV-85 specifies where the temperature setpoint is written
• AV-86 specifies where the occupancy override status is written
• AV-87 specifies where the battery status is written
Function
WTS Point
Default AZW-5000 Point
Temperature sensor reading
AV-80
AV-50
Temperature setpoint
AV-81
AV-51
Occupancy override status
AV-82
BV-52
Battery status
AV-83
BV-53