WGS Configuration
Rev A
Page 12
FlexZone Wireless Gate Sensor
Auxiliary Input Configuration
Supervision Specify the resistor supervision scheme used with the auxiliary security 
device.
Resistor 1 Specify the value of supervision resistor R1.
5k1
Resistor 2 Specify the value of supervision resistor R2 (available when dual resistor 
supervision is selected).
Noise Tolerance Used to compensate for noisy input wiring (0, 20, 40, 60, 80, 100 mV) when 
using single/dual resistor supervision on the auxiliary input. Set this parameter 
in conjunction with the Filter Window setting to reduce FAR/NAR.
40
Line Drop Used to compensate for the voltage drop on long or high resistance input 
wiring (0, 20, 40, 60 mV) available with single/dual resistor supervision.
0
Filter Window
(msec)
Specifies the time for which an input must remain active before an event is 
declared (0 to 2.5 s in 125 ms increments). Adjust the Filter Window in 
conjunction with the Noise Tolerance to reduce FAR/NAR.
250 msec
Control Activation
Alarm Specify a relay that will activate to signal an Auxiliary Input alarm condition 
(Local control mode or NM Mode).
Supervision Specify a relay that will activate to signal an Auxiliary Input supervision 
condition (Local control mode or NM Mode).