LC 1200 Manual                                                                                          Fire Panel Interface (FPI) 12-1 
Fire Panel Interface (FPI) 
  Specifications 
  Positioning and Mounting 
  Verifying the Fire Alarm Dry Contacts 
  Wiring 
  Terminals 
State codes require that all Locks, Elevator 
Deactivation, and Automatic Door Deactivation 
be wired into the facility’s fire alarm system. 
This is done so that in case of a fire, any 
restraint disengages, allowing for free egress or 
ingress. For more information on this policy, 
check your local codes. 
For each FPI unit (
Part #700013
Figure 12.1
used, you will need one set of dry contacts from 
the facility’s fire panel. Each FPI unit provides 
dry contact outputs for up to 8 LC units.  
 
In addition, the FPI unit can provide: 
  An Optional Central Override, which 
allows the facility to disable all Locks, 
Elevator Deactivation, and Automatic 
Door Deactivation units controlled by 
that FPI. Each FPI requires its own 
override switch. 
  A Manual Reset, which will re-engage 
the Locks, Elevator Deactivation, and 
Automatic Door Deactivation after the 
fire alarm is reset. This switch can be 
replaced with a jumper that will make 
the reset process automatic once the 
fire alarm is reset. 
  An Auxiliary Output (+12VDC) for 
alerting staff that the Locks, Elevator 
Deactivation, and Automatic Door 
Deactivation are disengaged. This is 
typically connected to the Staff Alert or 
Graphic Panel(s).