Load Specifications
Control
Load Type
Min. 
Load
Max. 
Load
SZ-6D
1
Incandescent
50 W
600 W
MLV
2
50 W / VA
450 W /  
600 VA
SZ-6ND
1
Incandescent
10 W
600 W
MLV
2
10 W / VA
450 W /  
600 VA
SZ-6ANS
3
Lighting
10 W / VA
6 A
Motor
0.083 A
3 A
 
  Notes
1  
Dimmer Load Type: SZ-6D and 
SZ-6ND are designed for use with 
permanently installed incandescent, 
magnetic low-voltage (MLV), or 
tungsten halogen only. Do not 
install dimmers to control standard 
receptacles or motor-operated 
appliances. 
2  Low-Voltage Applications: Use  
SZ-6D and SZ-6ND with magnetic 
(core and coil) low-voltage 
transformers only. Not for use with 
electronic (solid-state) low-voltage 
transformers. 
 
Operation of a low-voltage circuit 
with lamps inoperative or removed 
may result in transformer overheating 
and premature failure. Lutron strongly 
recommends the following: 
•  Do not operate low-voltage circuits 
without operative lamps in place.
•  Replace burned-out lamps as quickly 
as possible.
•  Use transformers that incorporate 
thermal protection or fused 
transformer primary windings to 
prevent transformer failure due to 
overcurrent.
3  Switch Load Type: SZ-6ANS is 
designed for use with all permanently 
installed lighting loads and with motor 
loads up to 1/4 HP (5.8 A).
Install in accordance with all local and 
national electrical codes.
Caution! These controls 
must not be used to control 
equipment that is not visible 
from every control location. 
They must also not be used to control 
equipment that could create hazardous 
situations such as entrapment if 
operated accidentally. Examples of such 
equipment which must not be operated 
by these controls include (but are not 
limited to) industrial doors, microwave 
ovens, heating pads, etc. It is the 
installer’s responsibility to ensure that 
the equipment being controlled is visible 
from every control location and that 
only suitable equipment is connected to 
these controls.
Environment: Ambient operating 
temperature: 32 to 104 °F (0 to 40 °C),  
0 to 90% humidity, non-condensing. 
Indoor use only.
Spacing: If mounting one control above 
another, leave at least 4½ in. (114 mm) 
vertical space between them.
Faceplates: Use Lutron Stanza 
faceplates for best color match and 
aesthetic appearance. Do not paint 
controls or faceplates.
Cleaning: To clean, wipe with a clean 
damp cloth. 
Do NoT use any chemical 
cleaning solutions.
Wallboxes: Lutron recommends using 
3½ in. (89 mm) deep wallboxes for 
easier installation. Several controls may 
be installed in one multigang wallbox 
— see Derating Chart.
RF Device Placement: RF dimmers 
and switches must be located within  
20 feet (6 m) of an RF signal repeater or 
a device configured as a repeater.
Stanza RF dimmers or switches cannot 
be controlled by the system until they 
are addressed and programmed. They 
will work as stand-alone controls only.
In multigang installations, several 
controls are grouped horizontally in one 
multigang wallbox.
When combining controls in a wallbox, 
derating is required.
Derating Chart 
Control
Load Type
End of 
Gang
Middle 
of Gang
SZ-6D, 
SZ-6ND
Incandescent
500 W
400 W
MLV
400 W /  
500 VA
300 W /  
400 VA
SZ-
8ANS
Lighting
5 A
3.5 A
Motor
3 A
3 A
 
Installation
Caution! Locate and remove 
fuse or lock circuit breaker in the 
OFF position before proceeding. 
Wiring with power ON may result 
in personal injury or death.
Short Circuit Check: Check the 
installation for short circuits before 
installing control(s). With power OFF, 
install standard mechanical switch(es) 
between hot and load. Restore power. 
If lights do not work or a breaker trips, 
correct wiring and check again. Install 
control(s) only when short is no longer 
present. Warranty is void if control is 
turned ON with a shorted circuit.
1.  Turn power OFF at fusebox or circuit 
breaker.
2.  Prepare wires. When making 
wire connections, follow the 
recommended strip lengths and 
combinations for the supplied wire 
connector.  
Note: Wire connectors provided are 
suitable for copper wire only.
   Wire Connector:
•  Strip insulation 3/8 in.  
(9.5 mm) for #14 AWG  
(1.5 mm
2
) wire
•  Strip insulation 1/2 in.  
(12.7 mm) for #16 or 18 AWG (1.0 mm
2
 
or 0.75 mm
2
) wire
•  Use to join one #14 AWG  
(1.5 mm
2
) or #12 AWG  
(2.5 mm
2
) ground wire with one #18 
AWG (0.75 mm
2
)  
control ground wire.
Twist wire connector tight. Trim or strip 
wallbox wires to the length indicated 
by the strip gauge on the back of the 
control. 
Push-In Terminals: 
Insert wires fully. Push-in 
terminals are for use with 
#14 AWG (1.5 mm
2
solid 
copper wire only. DO NOT 
use stranded or twisted 
wire. 
 
OR
Screw Terminals: Tighten 
securely to 5 in-lbs (0.55 
N•m). Screw terminals are 
for use with solid copper 
wire only. DO NOT use 
stranded or twisted wire.
3.  Wire controls as follows: 
Single location installation: See 
Wiring Diagrams 1 and 2. 
Power Booster and Interfaces: 
When using power boosters or 
interfaces, see wiring diagrams 
provided with the interface.
4.  Push all wires back into the wallbox 
and 
loosely fasten the control to the 
wallbox using the control mounting 
screws provided. Do not pinch the 
wires.
5.  Attach Lutron Stanza faceplate 
adapter and faceplate. 
  a.  Install faceplate adapter onto front 
of control(s).
  b.  Tighten control mounting screws 
until faceplate adapter is flush to 
wall (do not over-tighten).
  c.  Snap faceplate onto faceplate 
adapter, and verify that control is 
aligned properly.
  d.  If control(s) is (are) misaligned, 
loosen mounting screws 
appropriately. 
6.  Restore power. Check for correct 
local operation (see Dimmer 
Operation and Switch Operation).
Installation Instructions
Please Read Before Installing
Stanza
TM
Stanza
TM
 Dimmers
SZ-6D, SZ-6ND
Stanza
TM
 Switch
SZ-6ANS
120 V   50 / 60 Hz
Important Notes
Multigang Installations
Dimmer and 
Dimmer with Neutral
Switch
Middle of gang
End of gang
Control Location for Ganging
Mounting Diagram
Control 
mounting 
screws
Wallbox
Control
Included:
Wire Connector (1)
Mounting Screws (2)
Faceplate 
adapter 
mounting 
screws
Faceplate/adapter purchased 
separately.
FCC Information
Note: This equipment has been tested and found to comply with 
the limits for a Class B digital device pursuant to Part 15 of the 
FCC rules. Operation is subject to the following: (1) This device 
may not cause harmul interference, and (2) this device must 
accept any interference received, incouding interference that 
may cause undesired operation.