Lutron Electronics Company Inc 0110 Benutzerhandbuch

Seite von 4
Installation Instructions
Please Read Before Installing
GRAFIK T
T
Lutron Electronics Co., Inc.
7200 Suter Road
Coopersburg, PA 18036-1299  USA
Installation
1.
  CAUTION: To avoid overheating and possible damage to other equipment, do not use dimmers 
to control receptacles, fluorescent lighting fixtures, motor-operated appliances or transformer-
supplied appliances.
2.  Install in accordance with all national and local electrical codes.
3.  When no “grounding means” exist in wallbox, the NECR allows control without a grounding connection 
to be installed as a replacement if 1) a non-metallic, noncombustible faceplate is used with nonmetallic 
attachment screws or 2) the circuit is protected by a ground fault circuit interrupter (GFCI). For this type  
of installation, cap or remove the green ground wire on the dimmer/ switch, and only use a LutronR  
GraFIk TT wallplate.
4.  GraFIk TT controls are not compatible with standard 3-way switches. Use only with companion devices 
(GT-aD).
5.  Companion devices (GT-aD) cannot be used individually but must be used in conjunction with a GraFIk TT 
dimmer/switch in a multi-location application.
6.  In any multi-location circuit, use only one GraFIk TT dimmer/switch with up to four companion devices.
7.  GraFIk TT dimmer/ switch settings such as “Light Bar Intensity” and “Speaker On/Off” can be modified 
using advanced Programming Mode. For instructions and information on how to use advanced 
Programming Mode, please see LutronR application Note #534. 
Important Notes
120 V~  60 Hz
Recommended LEDs
CreeR:
 CR6 (499485)
Feit Electric:
 PAR38/LEDG5
PhilipsR: 9290002330 (426122); 9290002268 (424382); 9290002267 (424374) 
SylvaniaR: LED8PAR16/DIM/930/FL36/P/LW
For a complete list of compatible LEDs, please visit: 
www.lutron.com/LED
Multi-location – Lamps can be controlled from multiple locations.
One location will be replaced by a GraFIk TT dimmer/ switch and the other location(s) by a 
GraFIk TT companion device. The dimmer can be wired on the line-side or the load-side (if 
not using neutral wire). Switches and dimmers (if using neutral wire) must be wired on the 
line-side.
Dimmer / Switch
Connect the 
Green ground wire on the dimmer/ switch to the Green or bare ground wire in 
the wallbox (See 
Important Notes, number 3 at left).
Connect the 
Black
 wire on the dimmer / switch to the tagged wire removed from the switch. 
Connect the 
Red wire on the dimmer / switch to one of the remaining wires.
Connect the 
Blue wire on the dimmer / switch to the remaining wire.
Connect the 
White wire on the dimmer / switch to the neutral wire in the wallbox. 
Neutral wire connection is optional for GraFIk TT dimmers; however, the best dimming 
performance will be obtained when the neutral wire is connected. The neutral connection is 
required for GraFIk TT switches. always cap the white wire if a neutral wire is not present 
in wallbox.
Companion Device
Connect the 
Green wire on the companion device to the Green or bare ground wire in the 
wallbox (See 
Important Notes, number 3 at left).
Connect the 
Red wire on the companion device to the tagged wire and to the same color wire 
connected to the 
Red
 wire on the dimmer/switch.
Connect the 
Blue wire on the companion device to the remaining wire. 
6a
Ganging and Derating
When combining dimmers/ switches in the same wallbox, derating is required. No derating is required for 
companion devices.
1
   Designed for use with permanently installed LED, incandescent, tungsten halogen, or magnetic low-voltage 
only. 
2
   Power Boosters / Load Interfaces: If neutral connection is used, -G25LW and -G5ANSW models can control 
power  boosters / load  interfaces. For a list of compatible power boosters / load interfaces see LutronR  P / N 
369826, Compatible Power Boosters and Load Interfaces.
3
   Low-Voltage Applications: Use with magnetic (core and coil) low-voltage transformers only. Not recommended 
for use with electronic (solid-state) low-voltage transformers but ULR listed for dimmable ELV transformers. 
Operation of a low-voltage circuit with lamps inoperative or removed may result in transformer overheating and 
premature failure. Lutron strongly recommends the following:
  •  Do not operate low-voltage circuits without operative lamps in place.
  •  Replace burned-out lamps as soon as possible.
  •  Use transformers that incorporate thermal protection or fused transformer primary windings to prevent 
transformer failure due to overcurrent.
4
   When using the dimmer / switch to control MLV fixtures, the maximum lamp wattage is determined by the 
efficiency of the transformer, with 70%–85% as typical. For actual transformer efficiency, contact either the 
fixture or transformer manufacturer. The total VA rating of the transformer(s) shall not exceed the VA rating of 
the  dimmer / switch.
5
   Includes Mark XT, Tu-WireR, and POWERSENSER.
6
   Not for use with receptacles or appliances (e.g., garbage disposals). See LutronR Application Note #109 for 
compatibility with dimmed receptacles.
Control
Load Type
Not Ganged
End of Gang
Middle of Gang
rrT-G25LW 
1, 2
HQrT-G25LW 
1, 2
LED
250 W
Incandescent / Halogen
600 W
500 W
400 W
MLV 
3, 4
400 Va (300 W)
Dimmable Fluorescent 
5
3.3 a (400 Va)
LutronR Hi-lumeR a-Series LTE 
LED Driver
3.3 a 
10 driver maximum
rrT-G5aNSW 
2, 6
HQrT-G5aNSW 
2, 6
Lighting
5 a (600 W)
4.2 a (500 W)
3.3 a (400 W)
Fan
3 a (360 W)
Motor
3 a (1/10 HP)
Mixed
3 a (360 W)
Technical Assistance: www.lutron.com   |   U.S.A. 
|
 Canada 
|
 Caribbean: 
1.800.523.9466   |   Mexico:  +1.888.235.2910   |   Others:  +1.610.282.3800    •    For warranty details, please visit: www.lutron.com/TechnicalDocumentLibrary/warranty.pdf   |   For FCC/IC information, please visit: www.lutron.com/fcc-ic
Lutron and Tu-Wire are registered trademarks and FASS and GRAFIK T are trademarks of Lutron Electronics Co., Inc. 
   
|
   
NEC is a registered trademark of the National Fire Protection Association, Quincy, Massachusetts.
   
|
   
POWERSENSE is a registered trademark of Osram Sylvania, Inc.   |
   
Mark X is a registered trademark of Philips Lighting Electronics N.A., Inc.
   
|
   
© 2014 Lutron Electronics Co., Inc.
IMPORTANT
Cut the blue wire at the insulation and cap with the yellow 
connector. 
 English
Single-pole –
 Switch will be replaced by a GraFIk TT dimmer/ switch. 
Connect the 
Green ground wire on the dimmer/ switch to the Green or bare ground wire 
in the wallbox (See 
Important Notes, number 3 at left).
Connect the 
Black wire on the dimmer/ switch to one of the wires removed from the 
switch. If you had taped together two wires (see step 4), connect both wires to the 
Black 
wire on the dimmer/ switch and remove the tape.
Connect the 
Red wire on the dimmer / switch to the other wire removed from the switch.
Connect the 
White wire on the dimmer / switch to the neutral wire in the wallbox. 
Neutral wire connection is optional for GraFIk TT dimmers; however, the best dimming 
performance will be obtained when the neutral wire is connected. The neutral connection 
is required for GraFIk TT switches. always cap the white wire if a neutral wire is not 
present in wallbox.
8
9
7
5
2
remove wallplate and the switch mounting screws. Leaving all wires attached, carefully 
pull the switch out from the wall.
4
The switch may have two wires attached to the same screw. Tape these two wires 
together before disconnecting. Proceed to disconnect the wires from the switch. 
remove wallplate from the GraFIk TT dimmer/ switch and any companion device but 
leave wallplate adapter connected.
6
Install GraFIk TT control.
6b
Carefully push wires into the wallbox. Install controls and snap on wallplate. 
Turn ON power at circuit breaker.
1
Turn OFF power at circuit breaker.
If desired, consider adjusting low-end and high-end trim. See 
Operation for details. 
Troubleshooting
Symptom
Possible Solutions
Two LEDs are blinking.
•  Check wiring. If neutral wire is connected, ensure that the Black wire is 
connected to Live and the red wire is connected to Load.
•  Check wiring. Ensure that the Blue and red wires are connected as 
specified in 
Installation
Lamp and light bar LEDs do not turn on.
•   Push  FaSST up to restore power.
•  replace burned out lamp(s).
•  Turn ON breaker.
•   Check dimmer/ switch wiring (See 
Installation).
Unit is unresponsive.
•   Cycle power to unit by pulling the FaSST down and back up to fully 
restore power.
Lamps turn On and dimmer/ switch 
works but companion device does not 
work.
•  
Ensure that the wire connected to the Blue (or red) wire on the 
dimmer/ switch is the same as that connected to the Blue (or red) wire on 
the companion device (See 
Installation step 6b).
Lamps repeatedly turn On and Off.
•   See 
Minimum Load and ensure the acceptable minimum load is met.
Lamps flicker or exhibit poor dimming 
range.
•   Set low-end trim. See 
Operation for details. 
Wallplate is warm.
•   Solid-state dimmers internally dissipate about 1% of the total connected 
load. It is normal for dimmers to feel warm to the touch during operation.
Lamps don’t turn On / Off from a keypad.
•   Improper programming. Programming must be done through the system 
software. 
•   Out of rF range. reposition to be within 30 ft (9 m) of an rF signal 
repeater.
•   Wires shorted. Make sure the blue terminal is not grounded or shorted to 
any other wires. 
•   Wiring  error.  Ensure wiring matches installation instructions and 
appropriate wiring diagram.
Minimum Load 
1
  For performance or compatibility information, visit 
www.lutron.com/LED, which is constantly being updated.
2
  If using neutral wire, the minimum load required is one LED lamp or LutronR Hi-lumeR a-Series LTE LED Driver.
3
  If using neutral wire, the minimum incandescent/halogen load required is 5 W.
 
Switch
   recommended minimum load for the switch is 5 W or one SSL-7a compliant LED lamp. Loads not 
meeting this minimum requirement may need a LUT-MLC to function properly.
Dimmer
Load Type
Application
Number of Companion 
Devices
LED 
1, 2
Incandescent / Halogen 
3
Single-pole
0
2 LED lamps
40 W
Multi-location
1
3 LED lamps
80 W
Multi-location
2
4 LED lamps
120 W
Multi-location
3
5 LED lamps
160 W
Multi-location
4
6 LED lamps
200 W
120 V~
60 Hz
Black 
Ground
Red
Blue
Green
Neutral
Live
Load
3
Identify switch type. 
Single-pole – The switch will have insulated wires 
connected to two screws of the same color plus a 
green ground screw.
Multi-location – 3-way switches will have insulated 
wires connected to three screws plus a green ground 
screw. One of the wires is connected to a screw of 
a different color (not green) or labeled COMMON. 
Tag this wire. 
Tag
Ground
Different-colored screw
Ground
White
!
 
 
WARNING! Shock Hazard. May result in serious injury or death. 
Turn off power at circuit breaker before installing the unit.
Connect if 
using neutral 
wire
IMPORTANT NOTICE: FASST – Front Accessible Service Switch
To replace lamp(s), power may be conveniently removed by pulling the FASST down on the 
dimmer/ switch
. After replacing lamp(s), push the FASST back up fully to restore power to the 
dimmer/ switch
For any procedure, other than routine lamp replacement, power must be 
turned OFF at the main electrical panel.
Operation
 
Adjust:
  (Light Bar)
•   Touch to set lamps to 
desired level (Dimmer Only).
•  Slide to adjust light level 
(Dimmer Only).
•   Touch anywhere to toggle 
load  On / Off  (Switch Only).
 
Toggle On / Off:
•   Touch to turn Off or to turn 
On to previous light level.
•   Toggle button is white when 
On, orange when Off.
FASST : Front Accessible Service Switch
Note: FASST is not available on 
companion devices.
  Set High-End Trim: 
 
  (Dimmer Only)
1.  Press and hold top of light bar 
(approximately 6 seconds) until 
Toggle button flashes orange. 
2.  Slide finger on light bar to adjust to 
desired brightness. 
3.  To exit, press and hold the Toggle 
button (approximately 6 seconds) 
until the Toggle button stops 
flashing.
  Set Low-End Trim: 
 
  (Dimmer Only)
1.  Press and hold bottom of light bar 
(approximately 6 seconds) until 
Toggle button flashes orange.
2.  Slide finger on light bar to adjust 
to desired brightness. 
3.  To exit, press and hold the Toggle 
button (approximately 6 seconds) 
until the Toggle button stops 
flashing.
IMPORTANT
Wire connectors provided are for copper wires only. For aluminum 
wires, consult an electrician. 
Dimmers
LED
MLV
LutronR Hi-lumeR 
A-Series LTE LED 
Driver
1
Dimmable 
Fluorescent
2
Incandescent /  
Halogen
rrT-G25LW
HQrT-G25LW
250 W
400 Va (300 W)
3.3 a
1
3.3 a (400 Va)
600 W
1
   Ten (10) driver maximum.
2
 
 Includes Mark XT, Tu-WireR, and POWERSENSER.
Switches
Lighting
Fan
Motor
Mixed
rrT-G5aNSW
HQrT-G5aNSW
5 a
3 a
3 a (1/10 HP)
3 a
Companion devices
rT-GrDW
For use with rrT- dimmers and switches
HQT-GrDW
For use with HQrT- dimmers and switches
1
  Neutral wire connection is optional for GraFIk TT dimmers; however, the best dimming performance will be 
obtained when neutral wire is connected. The neutral connection is required for GraFIk TT switches. 
2
  The companion device is wired differently than a standard 3-way switch. Both the red wire and the tagged wire 
are connected to the same traveler wire. 
 
P/N 0301759 
Rev A
Tag 
Tag 
Live 
Live 
Dimmer/ Switch Line-Side (Dimmer or Switch)
Neutral 
1
Black 
Red 
Blue 
White 
Tag 
Blue 
Red
 
Green 
Green 
Ground
Ground
1
Load 
Ground
Black 
Red 
Blue 
White 
Green 
Blue 
Red
 
Green 
Ground
Load 
Neutral 
 2
 2
Dimmer Load-Side (without neutral wire)
Tag 
Neutral 
Connect if using neutral wire
Dimmer / Switch
Companion device
Dimmer 