Section 4: Other Programming
4.1 Program Zones and Partitions
Once all wireless devices are enrolled, complete zone programming on the system. Although the exact 
programming required varies depending on which control panel the TR5164 is connected to, ensure 
that the following programming options are completed correctly for each wireless zone:
• Enable zones and/or assign zones to one or more partitions (programming sections [202] to [265]).
• Program the definition for each zone (programming sections [001]-[004]).
• Enable the wireless zone attribute for each wireless zone (sections [101]-[164]).
Refer to the system Installation Manual for more information on the above programming sections.
4.2 Enable TR5164 Supervision 
The control panel can supervise the TR5164 receiver via the Keybus after at least one device has been 
enrolled on the module (Section 3.2, page 6). 
To activate module supervision: 
1. Enroll the first device(s).
2. Exit and then re-enter Installer Programming, [
,
][8].
3. Enter programming section [902]. Wait approximately 1 minute while the system scans for 
connected modules.
4. To exit press [#].
The system generates a General System Supervisory trouble if the module is removed from the 
Keybus. If the TR5164 module must be removed from an existing system, first disable TR5164 
supervision.
NOTE: Deleting all devices from the TR5164 or defaulting the TR5164 causes a supervisory 
fault.
To disable TR5164 supervision:
1. Disconnect the TR5164 from the Keybus.
2. Enter [
,
][8][Installer Code].
3. Enter [902]. The control panel clears all supervision and re-scans the system for connected 
modules. The scan takes approximately one minute.
4. To exit press [#].
To verify control panel supervision of the TR5164:
1. Enter [
,
][8][Installer Code].
2. Enter [903] to display all modules. On a LED 32 zone keypad, light [17] indicates that the TR5164 
is present on the system. On LCD keypads, scroll until the TR5164 module name is displayed.
3. To exit press [#].
If the TR5164 is not detected, check for one of the following problems:
• the module is not connected properly to the Keybus
• the Keybus wiring run is faulty
• the module does not have enough power
• no devices have been enrolled on the TR5164