Controller Operation 
AYC-Qx4 Family Installation and Programming Manual 
49 
For example, in Auxiliary Mode 8, the controller can function as a 
2-door controller and also provide LED indicator functionality control. 
The auxiliary relay is connected to the lock on the second door. The 
auxiliary setting defines the Door Open time for the second door. The 
auxiliary input is used to control the door indicator (right LED). If the 
auxiliary input is open, the right LED flashes green; if the auxiliary 
input is closed, the right LED flashes red. 
5.9.9.10
  Auxiliary Mode 9 
 
This mode controls the door indicator (right LED). 
The  right LED is not lit when: 
  A valid code is entered 
  While in Secure mode when waiting for Secondary code. 
Auxiliary input function: Red LED control 
Auxiliary output activated by: Valid user code, Auxiliary code 
For example, in Auxiliary Mode 9, the controller can function as a 
2-door controller and also provide LED indicator functionality control. 
The auxiliary relay is connected to the lock on the second door. The 
auxiliary setting defines the Door Open time for the second door. The 
auxiliary input is used to control the door indicator (right LED). If the 
auxiliary input is open, the right LED flashes red; if the auxiliary input 
is closed the right LED flashes green. 
5.9.10
  Setting the Lockout Feature 
If the controller is presented with wrong codes (PIN or card) 
consecutively several times, the unit goes into Lockout mode. 
When a lockout occurs, the controller keypad and reader are locked 
so no codes can be entered until the set lockout period expires. 
During Lockout, the left LED is Off, the right LED flashes red, and the 
controller beeps every two seconds. The default setting for the 
Lockout Feature is 4000 (Lockout Disabled). 
 
Using the lockout feature is highly recommended, especially 
when selecting to use short PIN code length (4 or 5 digits).