Rosslare Enterprises Ltd B8650 Benutzerhandbuch

Seite von 5
AY-B8650 
 
Anti-Vandal Fingerprint and 13.56         MIFARE RFID Reader
 
User Manual 
1.  Introduction 
The AY-B8650 series are biometric fingerprint and RFID card reader 
with a compact design, which is suitable for installing on a door 
frame. The USB power supply and debug make operations simple. 
The reader IP65 certified for outdoor use. 
Using AxTraxNG, you can register and delete users (see the 
AxTraxNG™ Software Installation and User Manual). Alternatively, you 
can use master cards to register and delete users while in an offline 
state. 
The standard Wiegand output seamlessly connects to the third-party 
access controllers. 
The reader comes in two models: 
 
 
AY-B8650 – 13.56 MHz MIFARE card reader 
Figure 1: AY-B8650 
2.  Installation 
2.1 
Mounting 
1.  Using the back panel as a guide, drill two holes for mounting 
the back plate onto the surface (Figure 2)
Figure 2: Wall Mounting 
 
2.  Insert a suitable wall plug into each screw hole. 
3.  Drill a 10-mm (7/16”) hole for the cable. 
4.  Screw the back plate onto the wall. 
5.  Connect the reader to the controller (see Section  2.2). A linear 
type power supply is recommended. 
6.  Attach the reader to the back plate and secure the reader to the 
back plate with the provided security screw and tools. 
2.2 
Wiring 
To connect the unit as a reader to an access control unit: 
1.  Select the appropriate connections according to Table 1. 
Table 1: Wiring the Unit as a Reader to a Control Panel 
Function 
Cable Color 
Description 
Power 
Red 
12 VDC 
Black 
GND 
Tamper Alarm  Brown 
Tamper 
Orange 
Tamper 
Wiegand 
Output 
Green 
Wiegand DATA0 Output 
White 
Wiegand DATA1 Output 
Blue 
Wiegand switch 
Black 
GND 
Pulse Signal 
Light brown 
RS-485B/GND 
Light Blue 
RS-485A/pulse signal (3.3 V) 
2.  Prepare the controller cable by cutting its jacket back about 
3 cm (1¼") and strip the insulation from the wires about 1.3 cm 
(½"). 
3.  Splice the reader’s pigtail wires to the corresponding controller 
wires and cover each joint with insulating tape. 
4.  Trim and insulate the ends of all unused conductors individually. 
Do not short any unused wires together. 
 
  The individual wires from the reader are color coded according the 
Wiegand standard. 
  When using a separate power supply for the reader, this supply 
and that of the controller must have a common ground. 
  The reader’s cable shield wire should be preferably attached to an 
earth ground, or a signal ground connection at the panel, or the 
power supply end of the cable. This configuration is best for 
shielding the reader cable from external interference. 
 
MHz