INNCOM International Inc. 027060TXR Benutzerhandbuch

Seite von 16
M O D E V A   R e f e r e n c e   M a n u a l  
P a g e   1 1   o f   1 6
 
 
 
Actuator 
Ratings 
 
Voltage 
Frequency 
Power / Amperes 
Load Type 
MOSFET 
Dimmer 
120 Vac 
60 Hz 
2.9 A 
Resistive 
120 Vac  
60 Hz 
2.9 A 
General Purpose 
120 Vac  
60 Hz 
350 W 
Tungsten / ELV 
120 Vac  
60 Hz 
250 VA 
Electronic Ballast 
7.2  Multigang Installation 
The MODEVA and Load Assembly comes in single, double and triple gang configurations; the double and triple 
gang assemblies may be any combination of relay, switches, MOSFET Dimmer or TRIAC Dimmer. The table 
below provides the derated output based on the configuration. 
Actuator 
Ratings 
 
Voltage 
Frequency 
Power / Amperes 
Load Type 
TRIAC Dimmer 
120 Vac 
60 Hz 
2.9 A 
Resistive 
120 Vac  
60 Hz 
2.9 A 
General Purpose 
120 Vac 
60 Hz 
400 W 
Tungsten 
120 Vac  
60 Hz 
250 VA 
Electronic Ballast 
MOSFET 
Dimmer 
120 Vac 
60 Hz 
2 A 
Resistive 
120 Vac  
60 Hz 
2 A 
General Purpose 
120 Vac  
60 Hz 
250 W 
Tungsten 
120 Vac  
60 Hz 
250 VA 
Electronic Ballast 
8  Multigang Installation Derating Chart 
8.1  Actuator Ratings 
Actuator 
Ratings 
TRIAC Dimmer 
Voltage 
Frequency 
Power / 
Amperes 
Load Type 
120 Vac 
60 Hz 
2.9 A 
Resistive 
120 Vac  
60 Hz 
2.9 A 
General Purpose 
120 Vac 
60 Hz 
400 W 
Tungsten 
120 Vac  
60 Hz 
250 VA 
Electronic Ballast 
MOSFET 
Dimmer 
Voltage 
Frequency 
Power / 
Amperes 
Load Type 
120 Vac 
60 Hz 
2 A 
Resistive 
120 Vac  
60 Hz 
2 A 
General Purpose