INNCOM International Inc. 202516TXR Benutzerhandbuch

Seite von 3
 
 
www.inncom.com
 
L506 Wireless Lamp Control  
Module Installation Guide 
The L506 FET 
dimmer can drive 
dimmable CFL 
loads and other 
loads: 
• 
100W 
Incandescent 
• 
35W Dimmable CFL or 100W 
incandescent equivalent 
• 
25W LED or 100W 
incandescent equivalent 
As an alternative to the L206 lamp 
socket module, the L506 provides 
wireless lamp control with a smaller 
footprint. Designed for standard 
medium lamp sockets (E26 Edison), 
the RF-equipped device can be 
controlled from any INNCOM IRAS 
device with an RF transceiver. The 
socket is equipped with a mechanical 
button that can control the load and 
assist in device binding. The L506 
series will eventually incorporate 
sibling products designed for other 
lamp socket types. 
Installation 
The installer must be a trained, 
experienced service technician. 
When installing this product: 
1.  Read the instructions carefully. 
Failure to follow them could 
damage the product or cause 
hazardous conditions. 
2.  Check the ratings given in the 
product guide to make sure the 
product is suitable for your 
application.. 
3.  Use the L506 module 
only with a recognized 
or listed lamp holder 
assembly. 
CAUTION: The distance 
between the bulb and the 
shade should be equal to or 
greater than required by the original 
UL listing for the lamp base. 
Improper placement is a fire hazard.  
Mounting  
The L506 may be mounted in 
vertical/bulb up, horizontal, or 
vertical/bulb down fixtures.
 CAUTION: 
The bulb-down orientation should 
generally be confined to open air 
installations; if used with a shade, the 
fixture should be further derated (see 
table below).  
1.  If the lamp’s Edison socket has a 
switch, make sure it is in the full 
on position, then remove or 
disable it. 
2.  The L506 dimmer-equipped lamp 
must be within 60 feet (indoors) of 
an RF transceiver/repeater. 
3.  Unplug the lamp cord from the 
power source (e.g., wall socket). 
4.  Remove any shade and lamp 
harp. 
5.  Remove the bulb; screw the L506 
dimmer/switch into the lamp 
socket. 
6.  Reinstall the bulb, then the lamp 
harp (if used). Rotate the harp if 
necessary to clear the L506 
socket. Plug the lamp back into 
the power supply. 
Derating: Do not exceed an ambient 
air temperature of 25˚C surrounding 
the L506 Lamp Controller when 
operating the lamp with the specified 
loads and orientations, as outlined in 
the following table.  
Maximum Ratings 
 
Vertical 
Base Down 
(bulb up) or 
Horizontal 
Vertical 
Base Up 
(bulb 
down)* 
Incandescent 
100W 
60W 
Dimmable 
CFL 
35W 
20W 
LED 
25W 
10W 
*Open air only. If fixture enclosed, further 
derating is necessary 
Communications 
The L506 can switch on a light using 
the built-in on/off button. For remote 
and dimming operation, the L506 
must be located within 60 ft. of an 
originating RF transmitter (any IRAS 
RF device can be configured as a 
repeater). The L506 must be 
commissioned. The outline below 
assumes the installer understands 
the commissioning process in 
general; specific commissioning 
procedures can be found on the 
property-specific commissioning 
sheet. 
Commissioning 
The L506 must be bound to an RF 
control device such as an e528 
thermostat.  
1.  The L506 enters bind mode for the 
first 2 minutes after powering up;