10.3. Cross Zone Verification 
Cross Zone Verification is use to setup cross verification for intrusion sensors.   
To use Cross Zone Verification, the following sensor and panel setting must be adjusted: 
1  At least 1 intrusion sensor must be set to Cross Zone attribute. 
2  The Cross Zone Timer option under Panel Setting webpage must be enabled. 
Cross Zone Verification Rule 
 
Cross Zone function does not activate under Exit and Entry Time. 
 
When a sensor set to Cross Zone attribute is triggered, the panel begins to sound alarm, 
counts down Cross Zone Timer and reports a Cross Zone First Trip event (CID 693). 
  If  the  Cross  Zone  Timer  expires  without  any  other  sensor  trigger,  the  panel  reports 
Cross Zone Trouble event (CID 378) when the timer expires. 
  If the same sensor is triggered again during Cross Zone Timers, the Cross Zone Timer 
is reset and extended. 
  If another sensor is triggered during the timer: 
 
The Panel report Burglar (CID 130) for both sensors. 
 
If the newly triggered sensor is set to Cross Zone attribute, the Panel also report 
Burglar Verified (CID 139) for this sensor. 
 
The Cross Zone Timer is reset and extended. 
 
When the Cross Zone Timer expires, the panel reports Cross Zone Timeout (CID 
694). 
 
10.4. Fire Verification   
Fire Verification is use to setup verification for Smoke Detector.   
To use Fire Verification, the following sensor and panel setting must be adjusted: 
1  At least 1 Smoke Detector must be set to 24 HR – Fire with Verification attribute. 
2  The Fire Verification Timer option under Panel Setting webpage must be enabled. 
Fire Verification Rule 
 
When  a  Smoke  Detector  set  to  Fire  Verification  attribute  is  triggered,  the  panel  begins  to 
sound alarm, counts down Fire Verification Timer and reports a Near Alarm event (CID 118). 
  Triggering  any  Smoke  Detector  with  Fire  Verification  attribute  (including  the  original 
Some Detector) during Fire Verification Timer will prompt panel to report Smoke Alarm 
event (CID 111), the timer will be reset and extended. 
  Triggering a regular Smoke Detector with Smoke attribute during the Fire Verification 
Timer will prompt panel to report Smoke Alarm event (CID 111), the timer will not be 
reset.. 
  When  the  Fire  Verification  Timer  expires,  the  panel  reports  Fire  Verification  Timeout 
event (CID 695).