The following image shows a long barrel double hole crimp lug:
...................................................................................................................................................................................................
3
Attach the ground cable to the 9768 MRO B4 chassis using the M6 hardware provided in
the ground kit (M6x16 screw, lock washer, plain washer).
Clean the contact surface area and use an antioxidant to avoid oxidation. Torque the M6
fasteners to 4.5 Nm (3.3 lb ft).
...................................................................................................................................................................................................
4
Route and attach the ground wire to the site ground system. An extra double hole crimp
lug, included in the ground kit, may be used if appropriate or the customer can provide
the necessary components to attach the ground wire to the site ground.
Clean the contact surface area and use an antioxidant to avoid oxidation.
Connecting the power connector
CAUTION
Electric-shock hazard
There is a danger of electric shock when the power cord is energized.
The connection/disconnection of the power cord to the 9768 MRO must be done only with
the power cord de-energized. De-energize the far end of the power cord from the power
source prior to disconnection at the 9768 MRO end.
Figure 3-20 Double hole lug
Long barrel double hole crimp lug
(1/4” hole, ¾” spacing)
Installing an 9768 MRO B4
Procedure 3-1: Installing the 9768 MRO B4 onto a wall or
pole
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
Alcatel-Lucent 9768 MRO
3MN-MRO-AWS-IMOP
Issue 1
February 2014
Alcatel-Lucent – Internal
Proprietary – Use pursuant to Company instruction
3-15
E
N D
O F