Transient load response
For any step-load demand change of 10% to 90%, or 90% to 10%, on the DC power
system, the DC input voltage to the Alcatel-Lucent B25 RRH4x30 shall remain within
5.0% and return to the 0.5% regulation band within 300 milliseconds.
Backup power requirements
In the event of a commercial power failure, Alcatel-Lucent recommends the DC power
provided to the Alcatel-Lucent B25 RRH4x30 be backed up for a minimum of 60
minutes. The DC power to the equipment shall not be interrupted during the transition
from normal operation to backup operation and vice versa.
High voltage shutdown
The DC power source may shut down if the output voltage reaches the following values:
Nominal voltage
Maximum voltage
range (Volts DC)
Maximum voltage for
up to one second
–48‑V DC
–56.2 to –60
–60
Notes:
1.
The DC power system shall not provide sustained voltage to the Alcatel-Lucent
B25 RRH4x30 at the maximum voltage values, for more than one second, as shown in the
table above.
2.
If a power system failure occurs which causes loss of regulation resulting in voltage levels
given in the table above stated as the “maximum voltage range,” the power system shall
shutdown or clamp its output voltage below –56.2‑V DC (for –48‑V DC systems) until the
problem is corrected.
Transient surge protection
The DC power system shall be designed to prevent surge transients at its input passing
through to the output and causing voltage transient in excess of –60 volts (for –48‑V DC
systems) to the Alcatel-Lucent B25 RRH4x30. Adequate transient surge protection must
be provided by the customer to limit surge voltages to less than –60 volts (for –48‑V DC
systems). If external surge protection is required to meet this limit, it should be installed
near the DC input terminal of the Alcatel-Lucent B25 RRH4x30.
DC power grounding
The –48‑V DC return conductors shall be bonded to the frame ground system at the
output of the DC power system. For proper site grounding of the equipment, refer to
Alcatel-Lucent's Grounding and Lightning Protection Guidelines for Alcatel-Lucent
Network Wireless System Cell Sites, 
401-200-115.
Electrical power requirements for –48V DC power systems
DC Power requirements
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
B25 RRH4x30