• Switch off all power supplies to the equipment before adding or removing power
connections.
• Installation must include an independent frame ground to the building ground. Refer
to the installation guide provided with the product.
• Ensure that the DC supply system is located within the same premises as the
equipment.
• Ensure that the equipment grounding is connected directly to the DC supply system
grounding electrode conductor or to a bonding jumper from a grounding terminal bar,
or bus, to which the DC supply system grounding electrode conductor is connected.
• Ensure that the equipment is located in the immediate area (such as adjacent cabinets)
as all other equipment connected to the grounded conductor of a common DC supply
circuit. The DC system must not be grounded elsewhere.
• Ensure that no switching or disconnection devices are located in the equipment
grounding conductor connected to the DC source grounding electrode conductor.
Safety
Basic safety aspects
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
1-6
Alcatel-Lucent – Proprietary