User alarm requirements
Overview
The Alcatel-Lucent B25 RRH4x30 supports up to four dry contact user alarms over one
connector. The customer’s user alarms must be dry contact form C. The B25 RRH4x30
can recognize an alarm state as being either open or closed (customer programmable),
with closed as the default. The user alarm connector can support up to 4 user alarms (2
pins each).
The alarm cables offered by Alcatel-Lucent are 15 m (50 ft) or 30 m (100 ft) long, and
consist of 4 twisted pairs of 24 AWG solid conductors and a 8-pin plug connector for the
Alcatel-Lucent B25 RRH4x30 end. The other end needs to be terminated at the punch
down block (provided by the customer). The user alarm ports are equipped with surge
protection.
User alarms wire colors and punch down positions
The following table lists wire color-coding and punch down information for the
Alcatel-Lucent B25 RRH4x30 user alarms:
Con-
nec-
tor
Pin #
Wire color
Designation
Comments
ALARM
1
White/Brown
User_ALM_4_P
2
Green
User_ALM_3_RTN
3
White/Blue
User_ALM_1_P
4
Orange
User_ALM_2_RTN
5
White/Orange
User_ALM_2_P
6
Brown
User_ALM_4_RTN
7
White/Green
User_ALM_3_P
8
Blue
User_ALM_1_RTN
Alarms interface
User alarm requirements
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
8-2
Alcatel-Lucent – Proprietary
Use pursuant to applicable agreements
B25 RRH4x30
3MN-02023-0001-RJZZA
Issue 0.02