E F Johnson Company 2422001-1 Benutzerhandbuch

Seite von 198
CIRCUIT DESCRIPTION
6-25
August 2000
Part No. 001-2001-200
Figure 6-9   NO LOAD CHARGE VOLTAGE vs. 
TEMPERATURE
6.6.3  REVERSE BATTERY PROTECTION
To obtain reverse battery protection a number of 
techniques were implemented.  Q108/Q110 are 
arranged in a Darlington configuration to isolate the 
output capacitors C109-C111 from conducting in the 
event the batteries are connected backwards.  This cir-
cuit also provides a means to turn the battery charger 
off in case the user wants to run the repeater off of 
another DC source.  S101 opens the base of Q105 
which turns off Q104.  CR111 is a green light emitting 
diode (LED) located on the right hand side of the bat-
tery back-up module when looking at the front of the 
power supply that tells the user the charger is in charge 
mode and is marked "On".
To notify the user that the batteries are connected 
improperly R101/CR101 are connected in series 
across the batteries.  CR101 is a red LED that lights 
when the batteries are connected backwards and is 
located on the left hand side of the battery back-up 
module when looking at the front of the power sup-
ply.  This LED is marked "Reverse Bat.".  CR113 
eliminates a path for the reverse battery current 
through the relay and over/under voltage protection 
circuitry.
NOTE:  Exceeding -30V across the battery back-up ter-
minals with the power supply on will destroy Q105.
6.6.4  ENGAGING THE RELAY
The main purpose of the Battery Back-Up Mod-
ule (BBM) is that when the power supply loses AC 
line voltage, a pair of series connected 12V lead acid 
batteries (approximately 26.4V) or other 23-28.5V DC 
source will engage to the supply allowing the repeater 
to operate.  To perform this function a voltage compar-
ator (U101) is used to monitor the charge tap coming 
from the power supply.  
A 2.5V reference voltage is supplied to the com-
parator from U102.  The transformer tap voltage is 
smoothed and divided by CR114, C118, R116, R121 
and R122.  The values for these components were cal-
culated so that when the AC line voltage is dropped to 
70V AC, the output of the comparator turns Q103/
Q102 on which in turn engages the relay K101.  The 
relay is capable of 30A which delivers the battery 
energy to the power supply via W102 with the return 
line being W103.  
NOTE:  When AC is restored, the relay disengages and 
the charger automatically begins to charge the batter-
ies.
6.6.5  OVER/UNDERVOLTAGE SHUTDOWN
U101 is a quad comparator IC used to create the 
overvoltage and undervoltage shutdown circuitry.  If 
the batteries are drained sufficiently enough such that 
the voltage of the batteries drops below 20.3V DC the 
output of the comparator goes low and turns Q102 off.  
By turning Q102 off the batteries are switched out of 
the circuit.  The batteries cannot be switched back into 
the repeater until the voltage rises to 22.6V DC.  This 
operation is in place to protect the repeater and the bat-
teries.  In the event the batteries are over charged, or 
the repeater is driven by the generator that has the 
voltage set too high, the relay will disengage above 
30.5V DC.  In order to switch the batteries back to the 
repeater, the voltage must drop below 29V DC.
In an overvoltage or undervoltage situation, 
whether AC is present or not, the red LED (CR105) 
lights until the problem is rectified.  This light is 
located on the right-hand side of the battery back-up 
module when looking at the front of the power supply 
and is marked BAT-BAD.
30V
27.3V
25.2V
24V
-30°
+30°
+60°
Temp (°C)
Charger Voltage
-55mV/°C
+22°