GEM-HEAT 
Wireless Heat Detector with Rate of Rise 
INSTALLATION INSTRUCTIONS
 
R
333 Bayview Avenue 
Amityville, New York 11701 
For Sales and Repairs, (800) 645-9445 
For Technical Service, (800) 645-9440 
© Napco 2004 
WI971B  2/04 
DESCRIPTION
 
The GEM-HEAT is a high-quality 135°F (57°C) Fixed 
temperature detector with Rate of Rise. It is compatible with the 
NAPCO Express and Gemini series GEM-RECV Series 
supervised security receivers.. 
 The GEM-HEAT incorporates circuitry which will transmit an 
alarm signal upon an alarm condition, generate an hourly 
supervisory test signal to the receiver and also monitor and 
annunciate low battery. 
Coding switches are not required or used in the GEM-HEAT. 
Each transmitter is assigned a unique identification code number 
at the factory. The transmitter is powered by one 3 Volt Lithium 
battery (supplied) which can power the unit for up to two years. If 
the battery voltage drops below normal, a low-battery report will 
be sent to the receiver with any status or alarm transmission. If a 
low-battery condition is indicated, replace the battery. 
 
OPERATION
 
Rate-of-Rise Feature:  A temperature increase of 15
0
F or 
more per minute will result in an alarm transmission. When the 
rate-of-rise element alone has been activated, the detector is self-
restoring. 
Fixed Temperature: If the temperature of the center disk 
rises to the detector’s rated temperature (135
0
F / 57°C)  an alarm 
transmission will result. When actuated by the fixed temperature 
element, the detector is non restorable and must be replaced. 
The need for replacement is indicated when the center disk has 
fallen free. Order Chemetronics model 601 to replace detector. 
When the GEM-HEAT detects an alarm as described above,  
the integral transmitter will send an alarm signal to the receiver. 
The alarm signal will be repeated every 10 seconds thereafter as 
long as the alarm condition is present. A restore report will be 
sent when the condition clears. Supervisory status reports are 
sent from the GEM-SMK every hour. 
Step 1. Remove the mounting base.  
Lift the GEM-HEAT from the base by turning the heat detector 
counter-clockwise while holding the base stationary. 
  
Step 4. Mounting the base to the ceiling 
Select mounting location for detector on ceiling. Do not locate 
in direct path of hot or cold air flow. Remove the protective 
insert from the base. Use the two screws and anchors 
provided to attach the mounting plate to the wall or ceiling.  
Reinstall the the protective  
insert into the base.  
 
NOTE: The mounting  
plate may be attached  
to a plastic single-gang  
electrical outlet box.  
Do not attach to  
metallic outlet  
boxes. 
Step 3. Install the battery 
Observing polarity, install the supplied Duracell DL123A 
battery. Reattach the circuit board to the mounting posts using 
the 4 Phillips head screws.  
 
 
 
DL123A  
Step 2. Remove the circuit board  
Remove the circuit board from the heat detector by removing 
the 4 Phillips head screws and carefully lifting the circuit board 
from the four mounting posts.  
 
 
 
 
 
NOTE: The RF ID#  
which appears on the  
circuit board label  
must be recorded in  
order to map the  
transmitter into the  
system. (see Step 7). 
RF ID#   7F545D5 : 7 
 
WARNING: NOT A LIFE SAFETY DEVICE - USE FOR PROPERTY PROTECTION ONLY 
NOTE: If the Auto-Enroll technique is to be 
used to map the transmitter, it must be 
done at the point the battery is installed. 
(Consult the control panel installation 
instructions for the Auto-Enroll procedure.) 
NOTE: Replace battery with Duracell  
DL123A Only. Use of another battery may 
present a risk of fire or explosion. 
BATTERY CAUTION: Risk of Fire, explosion and burns. Do not 
recharge, disassemble, heat above 100 deg. C., or incinerate. 
Dispose of used batteries promptly. Keep away from children.