Ever Superline 11 6kVA / 4.8kW W/SPRLTO-116K00/00 Benutzerhandbuch

Produktcode
W/SPRLTO-116K00/00
Seite von 7
ECO Pro CDS 
SUPERLINE 1-1
MODEL
Output power
1)
 
Working temperature 
2)
Input voltage distortionTHDi
Protection
Output voltage (RMS)
Output voltage waveform
Output voltage frequency
Output voltage distortionTHDu
Static voltage regulation 
Crest factor CF
Max. charging time of internal batteries
4)
 
Dimensions (width x depth x height)
UPS weight 
137 kg / 
200kg
Topology
Total efficiency for Pmax (for VFI)
Cooling
Work environment
Relative humidity when working 
Relative humidity during storage 
Altitude above sea level
 
3)
UPS backup time with 1 battery pack
(100 % / 80 % / 50 % Pmax)
model 6k
+10 ÷ +40 °C
<95%
<95%
<1000m
< 3%
~230 V ± 2 %
sinus
< 1,5% for Pmax (linear)
< 5% for Pmax; CF = 2.2; PF=0.65)
Inverter operation – electronic short circuit and overload
Operation from BYPASS line – input overvoltage protection
< 2h
340x740x795mm
synchronous
 / 50 Hz ± 0,2 Hz
< 1 %
>93%
forced, internal fans
rooms marked by a low contamination level 
VFI
Circuit breakers for the main line and BYPASS 2 x 63 A (ch.B)
SUPERLINE
Total efficiency for Pmax (for ECO)
>98%
Protection level 
Ip20
Short circuit current
Protection
Maximum charging time of 1 pack
(after recharging with the power of 80% Pmax)
4)
 
< 2h
5:1
> 5 I
N
< 2h
< 3h
< 3h
< 3h
6-11, 8-11, 10-11, 12-11
model 8k
SUPERLINE
model 10k
SUPERLINE
model 12k
SUPERLINE
6kVA / 4,8kW
8kVA / 6,4kW
10kVA / 8kW
12kVA / 9,6kW
Storage temperature
0 ÷ +40 °C
Input voltage
Input voltage frequency
Power factor PF
~70 ÷ 280 V ± 2 %
> 0,99
45 ÷ 55 Hz ± 1 Hz
INVERTER
Backup time from internal UPS batteries 
(100 % / 80 % / 50 % Pmax)
Pack batteries
5)
 
2 x 28 x VRLA 12 V / 7 Ah
< 2h
< 3h
12/21/35 min
24/32/54 min
7/10/12 min
10/14/25 min
7/10/15 min
13/17/30 min
72/95/180 min
30/42/74 min
40/51/92 min
9/12/25 min
17/22/40 min
50/72/125 min
FITTINGS
Terminals
Indication
Communication interface
EPO
Manual BYPASS switch
2
screw terminals; max. 16 mm
 
(wire)
sound and LED, LCD 
RS 232, USB, 
SNMP/ HTTP network management/card - option
prov
prov
1) For standard UPS operation, the load that is applied to the output may not exceed 80% of the value in the table.
The power margin is necessary to ensure continuous work of the connected devices in the case of instantaneous surges of the load's current.
2)Permanent exposure of the UPS to the ambient temperature in excess of +25°C reduces the battery life.
3)When the altitude above sea level rises in excess of the specified limit, the allowed power of the load on the UPS is reduced.
4) Charging time to reach 90% of the battery capacity, prior to discharging with a load equal to 80% Pmax.
5) Example of a battery pack in a typical configuration
MECHANICAL PARAMETERS
RECTIFIER
UPS batteries
1 x 28 x VRLA 12 V / 7 Ah 
2 x 28 x VRLA 12 V / 7 Ah 
(option)
BATTERIES
Note! 
The manufacturer reserves the right to modify the above parameters without notice.