2600T Series Pressure transmitters | OI/266/WIHART-EN   27
6 Transmitter connection
Important. HART hand-held communicator may be connected 
at any termination point in the loop. No need of 250 ohms 
resistance for communication purposes.
6.4 Supply requirement
Pressure transmitter power supply is granted by a 3.6V size ‘D’ 
battery. Standard supplied battery is a Lithium-thionyl chloride 
cell certified for Hazardous Areas.
6.5 Powering the transmitter on
Follow these steps to power the transmitter on:
  — Remove the temporary plastic cap from one of the two    
    electrical connection ports located at both sides in the    
    upper part of the transmitter housing.
  — This connection port has a M20 threads. Dedicated plug   
    has to be fitted to this port to comply with plant standards.
Important. 266 Pressure Transmitter is certified IP67. To 
maintain the IP67 certification rating, it is necessary to select 
the dedicated plug.
  — Remove the housing cover of the “field terminals” side.    
    See the indication engraved on one side of the housing.
  — Remove the battery pull-tab grabbing it firmly and pulling   
    it completely outside from its slot. This will allow the cell to  
    make contact with the electronic module.
Note. 266 WiPressure battery is manufactured by TADIRAN 
Batteries GmbH (manufacturer code SL 2780)
 — 
Before installing the huosing cover, check whether the    
    display is working or not. If yes, put back the housing    
    cover, turn it to seat O-ring into the housing and then    
    continue to hand tighten until the cover contacts the  
 
    housing metal-to-metal. 
6.6 Protective Grounding
Pressure transmitter housing should be grounded or earthed in 
accordance with national and local electrical codes. Ground 
connection is mandatory for surge protector equipped devices 
in order to ensure proper functioning.
Protective grounding terminals (PE) are available outside and/or 
inside the housing of the transmitter. Both ground terminals are 
electrically connected and it up to the user to decide which one 
to use. The most effective transmitter case grounding method 
is direct connection to earth ground with impedance equal or 
less of 5 ohm.
6.3 HART
Figure 31: HART transmitter connection scheme
2
3
4
1
1 Handheld communicator | 2 External ground termination 
point | 
3 Battery | 4 Fast connection for harvesting unit