ABB WICB Benutzerhandbuch

Seite von 72
36   OI/266/WIHART-EN | 2600T Series Pressure transmitters
7 Commissioning
7.9 Commissioning by DTM
The 266WiPressure DTM gives access to all parameters and 
information relevant to communication and device 
commissioning. Once the device is taken into the wireless 
network by the gateway the DTM can be used with the wired 
but also with the wireless interface, depending of the 
capabilities of FDT frame application and gateway. 
Typically the connection to the gateway is via Ethernet. This 
allows a remote access to the wireless HART network and the 
266 WiPressure over intranet or Ethernet, depending on the 
network policies. Components and tools provided or 
recommended by ABB do not have limitation regarding the 
communication interface.
Usually the network ID and join key needs to be set to allow a 
wireless device to enter an existing network. The join key and 
the network ID are also set in the gateway and must be the 
same as that entered in the 266 WiPressure.
The following description assumes the device needs a change 
of network parameters to join a network.
The DTM will have to be connected via a wired interface to the 
266 WiPressure. After searching for the device and getting into 
online mode the dialog Network Settings should be opened:
The sequence of the adjustments is as the position of the 
parameters with the DTM dialog:
  1.   Network ID to be set in decimal notation within the DTM.
  2.  Join key to be set in hexadecimal notation
  3.  Join mode. Usually the option “Join now” is most suitable  
    to let the device enter the (new) network after download all  
    parameters described above.
The data on the bottom of the dialog gives status information 
about the process of network join. Whenever a wireless HART 
network is in the range of 266 WiPressure – even it does not 
match its own network parameters -  the “Wireless signal 
found” flag is set. This is a pre-condition to join a network. The 
266 WiPressure now tries to join the network and to establish a 
connection to the wireless HART gateway. 
A successful join phase is indicated by the “Join complete” flag 
at the end. Depending of the network structure, size and 
performance of wireless HART gateway and other devices in 
the network it may take up to 60 minutes.
Important. Some gateways need to switch on the “Active 
Advertising” in order to support devices to join the network. 
7.9.1 Network Diagnostics by DTM
One of the strengths of wireless HART networks is the 
capability to automatically build a robust meshed structure. So 
the wireless devices try to connect to neighbours in order to 
get multiple paths for any telegram. 
Powerful network diagnostics of 266 WiPressure automatically 
checks the network transmission quality to and from the device 
itself.DTM gives visibility about signal strenght for at maximum 
five neighbour devices showing their specific link.
Signal strength is returned as a computed value which includes 
signal level, retries required etc.
Important. In a proper and robust network, each wireless 
device should have at least three neighbours.
Figure 35: Burst B2 in OFF-OFF status