62   OI/266/WIHART-EN | 2600T Series Pressure transmitters
10 Maintenance
  — Respect the below table indications for reinstalling the process flanges.
Transmitter model and range
Procedure
266DSH / PSH / VSH
Viton Gaskets All bolting
Use a torque wrench to tighten the bolts to a torque of 25 Nm.
PTFE Gaskets
Carbon Steel NACE 
and Stainless Steel
Use a torque wrench to tighten the process flange nuts to a torque of 40 Nm, let the flange 
stabilize for an hour, unscrew the nuts and tighten again to 25 Nm.
Stainless Steel 
NACE
Use a torque wrench to tighten the process flange nuts to a torque of 25 Nm, let the flange 
stabilize for an hour and perform the final tightening to 25 Nm.
266DSH.x.H  
(High static option)
Viton Gaskets All bolting
Use a torque wrench to tighten the bolts to a torque of 31 Nm.
PTFE Gaskets All bolting
Use a torque wrench to tighten the process flange nuts to a torque of 40 Nm, let the flange 
stabilize for an hour, unscrew the nuts and tighten again to 31 Nm.
266DSH range A 
(1KPa)
All gaskets
All bolting
Use a torque wrench to tighten the process flange screws/nuts to a torque of 14 Nm. Please be 
aware that in case of bottom work disassembly and reassembly the original performances can not 
be guarantee anymore.
266DSH with Kynar 
inserts
All gaskets
All bolting
Use a torque wrench to tighten the process flange screws/nuts to a torque of 15 Nm
10.4 Pressure transducer replacement
If the pressure transducer needs to be replaced proceed as 
follows:
  1.   Insulate the transmitter from the process by acting on the    
   
manifolds or on the insulation valves.
  2.   Open the vent valves to allow sensor depressurization.
  3.   Remove the battery.
  4.   Disconnect the transmitter from the bracket unscrewing the  
   
fixing bolts.
  5.   Open the communication board compartment cover.
  6.   The communication board is connected to the sensor via a  
   
flat cable and a connector. Remove the communication    
   
board and gently disconnect the connector.
  7.   Release the tang screw until nd rotate the housing until its   
   
complete removal.
  8.   Unscrew the fixing bolts from the transducer and remove    
   
the process flanges.
  9.  The orings placed between the diaphragm and the flange    
   
(Viton or PTFE) must be replaced after every disassembly.
  10. Reassemble the flanges following the steps above in  
 
   
reverse order.
  11. The 266 can reconfigure itself with the previous configured  
   
parameters thanks to the auto-configuration functionality.
  12. Before powering on the transmitter raise dip-switches 1 and  
   
2 in up position. Install the battery, wait ten seconds and    
   
lower dip-switched 1 and 2 .
  13. After installing the transmitter on the bracket and   
 
   
connecting it to the manifold, performe a PV zero bias.
10.5 Electronic replacement
If the electronic module needs to be replaced proceed as follows:
  1.   Insulate the transmitter from the process by acting on the    
   
manifolds or on the insulation valves.
  2.   Open the vent valves to allow sensor depressurization.
  3.   Remove the battery.
  4.   Open the communication board compartment cover and    
   
remove the LCD display (if installed).
  5.   Remove the communication board and gently disconnect    
   
the connector.
  6.  Connect the sensor flat cable to the new electronic module  
   
with dip switch 1 in up position.
  7.  Connect the transmitter to power supply, wait ten seconds  
   
and lower dip-switch 1 to 0 position. 266 can reconfigure    
   
itself with the previous configured parameters thanks to the  
   
auto-configuration functionality. 
10.6 Battery replacement
  1. Remove the housing cover of the “field terminals” side.    
    See the indication engraved on one side of the housing.
  2. Remove the battery and pulling it completely outside from  
    its slot. 
  3. Replace the battery paying attention to the polarity and    
    assuring that the cell makes contact with the electronic    
   module.
Note. 266 WiPressure battery is manufactured by TADIRAN 
Batteries GmbH (manufacturer code SL 2780)
 4. 
Before installing the huosing cover, check whether the    
    display is working or not. If yes, put back the housing    
    cover, turn it to seat O-ring into the housing and then    
    continue to hand tighten until the cover contacts the  
 
    housing metal-to-metal. If display is not working, please   
    refer to the troubleshooting section.