LED Behavior 
When the Stealth Reader is activated, two LED indicators provide visual status information.  With a few 
exceptions, the Red LED generally provides status information regarding the connection between the Stealth 
Reader and the water register; the Green LED provides status information regarding the communication link 
between the Stealth Reader and the Fixed Wireless Network. 
 
The following chart identifies the status information a Stealth Reader may provide: 
 
Red Light 
Green Light 
Status 
Action 
Fast Blink 
Off 
No application firmware installed 
Return for service 
Off 
Fast Blink 
Date and Time not set 
Proceed with installation, check Stealth 
Reader battery and alarm status at end of 
installation. 
Slow Blink 
Active 
No register detected 
Check register wiring/connections 
Fast Blink 
Active 
•  Encoded register: error 
reading register 
•  Pulse register: fewer than 5 
pulses received 
•  Encoder: check wiring/connections 
•  Pulse: may be OK, if possible advance 
register to generate several pulses 
On 
Active 
•  Encoded register: read OK 
•  Pulse register received 5 or 
more pulses 
See below for actions based on Green LED 
Active 
Slow Blink 
Searching for fixed network 
May be OK, but if persists may require 
installation of a repeater or additional Stealth 
Readers nearby.  Neighbor swiping is 
recommended. 
Active 
Fast Blink 
Found fixed network, waiting to 
register/re-register. 
May be OK, if persists may require 
installation of a repeater or additional Stealth 
Readers nearby.  Neighbor swiping is 
recommended. 
Active 
On 
Fixed network found and 
successfully registered. 
See above for actions based on Red LED 
On 
On 
Fixed network found and 
successfully registered 
Water register found and 
connected 
No action, install successful! 
On 
Off 
Status for one second indicates 
detected magnet activation 
No action 
Note: 
“Active” indicates slow blink, fast blink, or steady on.