Procedures  to  run  2  generators  with  a 
parallel box: 
1.  Prepare  two  KIPOR IG2000 I  digital 
generators. 
 
Figure 2 
Note: 
Be sure the two generators are shut off. 
 
2.  Insert  the  connecting  plug 
  of  the  parallel  cable 
  to  PARALLEL  OUTPUT 
receptacle 
  on the controller panel of each generator
See figure 3
 
3. Connect the grounding terminal 
  of the parallel cable to the grounding terminal 
  of each generator
See figure 3
 
 
 
Figure 3 
 
 
  Be sure all the electrical equipment is grounded. See 
  Be sure each generator is on a stable level surface. 
 
4. Start the two generators: 
The  start  procedure  is  the  same  as  normal  start  procedure.  (Refer  to  the  section 
introducing how to start the engine in this manual)