INSTALLATION
EATON Two-in-One PPDM (5000/6000 VA) User's Guide  
S
  164201820 Rev 1  www.eaton.com/powerquality
14
UPS Shutdown
If the UPS is already installed and operating, shut down the UPS:
1.
Prepare your equipment for shutdown.
2.
Press the 
button for approximately three seconds.
The UPS beeps once, and the load is no longer protected by the
UPS. It is powered by utility power. If the UPS is set in frequency
converter mode, the equipment will not be powered.
If the utility power is out of tolerance, the UPS will generate a
10 ms output calibrated break.
3.
For a full shutdown of UPS and connected load, the upstream
circuit breaker (not included) should be set to the OFF position.
4.
Continue to the following section, “PPDM Setup.”