Intel E5-2403 CM8062001048300 Benutzerhandbuch

Produktcode
CM8062001048300
Seite von 258
Intel® Xeon® Processor E5-1600/E5-2600/E5-4600 Product Families
255
Datasheet Volume One
Boxed Processor Specifications
10.3.1
Boxed Processor Cooling Requirements
As previously stated the boxed processor will have three thermal solutions available. 
Each configuration will require unique design considerations. Meeting the processor’s 
temperature specifications is also the function of the thermal design of the entire 
system, and ultimately the responsibility of the system integrator. The processor 
temperature specifications are found in 
 of this document.
10.3.1.1
STS200C (Passive / Active Combination Heat Sink Solution)
The active configuration of the combination solution is designed to help pedestal 
chassis users to meet the thermal processor requirements without the use of processor 
chassis ducting. However, it is strongly recommended to implement some form of air 
duct to meet memory cooling and processor T
LA
 temperature requirements. Use of the 
active configuration in a 2U rackmount chassis is not recommended.
In the passive configuration it is assumed that a chassis duct will be implemented. 
For a list processor and thermal solution boundary conditions, such as Psi
ca
, T
LA
airflow, flow impedance, etc, see 
. It is recommended that 
the ambient air temperature outside of the chassis be kept at or below 35 
°
C. Meeting 
the processor’s temperature specification is the responsibility of the system 
integrator.This thermal solution is for use with processor SKUs no higher than 150W (8 
Core) or 130W (4 and 6 core).
10.3.1.2
STS200P and STS200PNRW (25.5mm Tall Passive Heat Sink Solution) 
(Blade + 1U + 2U Rack)
These passive solutions are intended for use in SSI Blade, 1U or 2U rack configurations. 
It is assumed that a chassis duct will be implemented in all configurations. 
For a list processor and thermal solution boundary conditions, such as Psi
ca
, T
LA
airflow, flow impedance, etc, see 
. It is recommended that 
the ambient air temperature outside of the chassis be kept at or below 35 
°
C. Meeting 
the processor’s temperature specification is the responsibility of the system integrator.
These thermal solutions are for use with processor SKUs no higher than 130W (6 and 8 
Core), or 80W (4 Core).
Note:
Please refer to the Intel® Xeon® Processor E5-1600/E5-2600/E5-4600 Product 
Families Thermal/Mechanical Design Guide
 for detailed mechanical drawings of the 
STS200P and STS200PNRW.
Figure 10-12. Fan Cable Connector Pin Out For 4-Pin Active Thermal Solution