Step 3 - Other P4000 SANs Options
Description
Two 6' Highline (IEC-IEC) power cord ships standard per P4300/P4500 Node
NOTE: HP P4300/P4500 Storage Systems servers no longer ship standard with NEMA power cords (P/N 163719-002) that allow
connection to 110V US wall outlets in a home or office. HP P4000 Storage Systems are primarily connected to PDU's in data center
racks so they now ship standard with only a PDU power cord (416151-B21). If a user wishes to power a HP P4000 Storage Systems
using a 110V receptacle (NEMA-15), the NEMA power cord (AF556A) must be ordered separately. If customers require a power cord,
they can check the power cord matrix for the appropriate cord. Please see the UPS and PDU cable matrix's on the Power Protection
page under Power Cords that lists cable descriptions, requirements, and specifications for UPS and PDU units at the new HP Power
Cord Link @ HP.com. Use the following new link:
 
NOTE: Rack models ship standard with IEC cables.
Step 4 - Choose Supported Options For iSCSI Infrastructure
Select each required option with quantities specified. The P4000 G2 SANs support servers with industry standard Gigabit and 10 Gigabit
(SFP+) Ethernet components from various manufacturers that conform to IEEE 802.3ab (1000base-T) standards.
Description with Parts Shipped:
For details on standard Gigabit Ethernet components (including Gigabit Ethernet switches, Network Interface cards and Ethernet
cables) from HP 
Step 5 - Choose Rack Options
Select each required option with quantities specified.
Rack Airflow
Requirements
Rack 10000 G2 series Cabinets The increasing power of new high-performance processor technology
requires increased cooling efficiency for rack-mounted servers. The 10000 G2 Series Racks provide
enhanced airflow for maximum cooling, allowing these racks to be fully loaded with servers using the
latest processors.
CAUTION: If a third-party rack is used, observe the following additional requirements to ensure adequate
airflow and to prevent damage to the equipment: Front and rear doors: If your 42U server rack includes
closing front and rear doors, you must allow 830 square inches (5,350 sq cm) of hole evenly distributed
from top to bottom to permit adequate airflow (equivalent to the required 64 percent open area for
ventilation). Side: The clearance between the installed rack component and the side panels of the rack
must be a minimum of 2.75 inches (7 cm).
CAUTION: Always use blanking panels to fill all remaining empty front panel U-spaces in the rack. This
arrangement ensures proper airflow. Using a rack without blanking panels results in improper cooling that
can lead to thermal damage.
Rack Kit HP P4000 G2 rack models have fixed rails which provide support for racks with round mounting
holes and tool-free support for racks with square mounting holes (including Compaq/HP 7000, 9000,
10000 and HP series), with an adjustment range of 26" - 36".
Telco Rack Support - Support for all 2 and 4 post Telco racks and threaded hole racks requires an
additional option kit from Rack Solutions. The Rack Solutions brackets can be purchased at:
NOTE: Cat5e cables are required to connect Interface Adapters to Console Switches. Cat5e cables can be
found at the following URL: 
.
NOTE: It is mandatory to use a shock pallet when shipping racks with equipment installed.
QuickSpecs
HP P4000 G2 LeftHand SAN Solutions
Configuration Information
DA - 13552   North America — Version 23 — October 19, 2012
Page  36