     RS-422 & RS-485 High Energy Surge Protector   
Model 422HESP 
 
The Model 422HESP is designed to help protect against 
lightning strikes, power surges, and other types of voltage 
disturbances.  Five RS-422/485 signals on terminal blocks are 
supported with a clamping voltage of approximately 6.8 volts.  
The 422HESP offers three stages of protection starting with a gas 
discharge tube followed by a series resistor and finally a 
Transient Voltage Suppresser (TVS).  In order for a surge 
protector to work properly it is important to have a good 
connection to earth ground.  The 422HESP offers two terminal 
posts and two metal mounting brackets which provide a good 
ground connection for the user.  The 442HESP has been tested 
to two specifications at 6 kilovolts, IEC 1000-4-
5:  1995 “Surge 
Immunity Test” and IEEE C62.41-1991 “IEEE Recommended 
Practice on Surge Voltages in Low-
Voltage AC Power Circuits”.  
To ensure the best protection of your equipment some simple 
connection guidelines should be followed. 
 
Connections 
1.   The 422HESP should be located as close as possible to the equipment being protected.   
2.   A good ground connection must be made between the 422HESP and earth ground.  This can be done 
with the two terminal posts on the top of the unit or the two mounting brackets. 
3.   The earth ground connection should be kept as short as possible for best performance.  As a 
recommendation a minimum of 10 gauge copper wire at no more than 3 feet should be used.  If it is 
not possible to achieve the short distance a braided cable made specifically for grounding purposes 
should be used.  
4.   The chassis ground of the equipment should be connected to the buildings 3 prong plug ground.  
 
Specifications 
Clamping Voltage, stage one: 
Min. 72 VDC, Max.108 VDC 
Series Resistance, stage two: 
2.7 Ohms 
Clamping Voltage, stage three:  Min. 6.45V,  Max 7.14 V 
Clamping Time:  
 
Less than 5 x10
-9 
seconds 
Connectors: 
 
 
5 Position Terminal Blocks 
Dimensions:  
 
 
Approximately 11.4 x 8.4 x 4.6 cm (4.5”L X 3.3”W X 1.8”H) 
Weight:  
 
 
Approximately .19 kg (6.7 ounces) 
 
 
 
 
DECLARATION OF CONFORMITY 
Manufacturer’s Name: 
B&B Electronics Manufacturing Company 
Manufacturer’s Address: 
P.O. Box 1040 
 
707 Dayton Road 
 
Ottawa, IL  61350  USA 
Model Numbers: 
422HESP 
Description:   
RS-422/485 High Energy Surge Protector 
Type: 
Light industrial ITE equipment 
Application of Council Directive:  89/336/EEC 
Standards: 
EN 50082-1 (IEC 801-2, IEC 801-3, IEC 801-4) 
 
EN 50081-1 (EN 55022, IEC 1000-4-2) 
 
EN 61000 (-4-2, -4-3, -4-4, -4-5, -4-6, -4-8, -4-11) 
 
ENV 50204 
 
EN 55024 
 
Robert M. Paratore, Director of Engineering 