E6581741 
- 75 - 
 
10.3. Configuring Modbus messaging 
To use Modbus messaging in PL7, the “IP address”, “Subnet mask” and “Gateway 
address” parameters must be configured in the “Messaging” tab in the PLC Ethernet 
module configuration screen. 
Data entered in the “Connection configuration” box is used to manage the PLC Modbus 
messaging service, but has no effect on IO Scanning which is an independent service. 
 
 
Example: 
 
PLC IP address 
192.168.1.30 
Subnet mask 
255.255.255.0 
Gateway address 
0.0.0.0 
Drive IP address 
192.168.1.12 
 
 
Xway address 
IP address 
Protocol 
Access 
Mode 
1,101 192.168.1.12 MODBUS 
;
 
MULTI