ELECTRICAL WIRING (MILLI-VOLT)
A. COMPLETE MILLIVOLT SYSTEM CHECK 
 
  (“A” Reading - Thermostat contacts CLOSED - Control Knob “ON” - Main burner should turn ON)
 
a.  If the reading is more than 100 milli-volts and the automatic valve still does not come on, replace the control.
 
b.  If the closed circuit reading (“A” reading) is less than 100 millivolts, determine cause for low reading, proceed to 
Section B below. 
B. Thermopile Output Reading Check 
(“B” Reading - Thermostat contacts OPEN - Main burner OFF)
 
1.  Check gas pressure to the unit. If gas pressure is within minimum and maximum on data plate, then check pilot 
voltage, 325 millivolts minimum. If the minimum milli-volt reading is not obtainable, replace pilot.
 
 
 
CONNECT
 
  METER 
SWITCH 
OR 
METER
 CHECK 
TO 
LEADS TO 
THERMOSTAT 
READING
 TEST 
TEST 
TERMINALS 
CONTACTS 
SHOULD 
BE
 
COMPLETE 
2 & 3 
CLOSED 
CLOSED
  
SYSTEM
 
THERMOPILE 
1 & 2 
OPEN 
OPEN
  
OUTPUT 
CHECKING SYSTEM OPERATION
The milli-volt system and individual com-
ponents may be checked with a milli-volt 
meter having a 0-1000 mV range. Conduct 
each check shown in chart below by con-
nection meter test leads to terminals as 
indicated.
CONNECTING REMOTE RECEIVER (Figure 21)
THESE INSTRUCTIONS SUPERCEDE THE SECTION 
ENTITLED “HEARTH MOUNT” IN THE MILLI-VOLT 
HAND-HELD REMOTE INSTRUCTIONS SUPPLIED 
WITH THE REMOTE.
1.  Remove cover on control panel to show opening for remote 
receiver
2.  Connect the remote connectors located in the unit.
3.  Slide remote receiver in the opening of control panel. Use 
two screws provided to attach remote receiver to the control 
panel. 
4. Replace Cover. 
NOTE: Do not place remote in combustion chamber. 
Figure 21 - Installing Remote Receiver 
Remote 
Receiver 
Cover  