Figure 7. The water heater should have clearances of at least 1 inch 
(25 mm) from the sides and back and 6 inches (150 mm) from the front
of the appliance. The opening should directly communicate with the 
outdoors or should communicate through a vertical or horizontal duct 
to the outdoors or spaces that freely communicate with the outdoors 
and should have a minimum free area of the following:
1.  1 square inch per 3000 Btu/hr (700 mm
2
per kW) of the total input
rating of all appliances located in the enclosure, and
2.  Not less than the sum of the areas of all vent connectors in space.
outdoor aIr throuGh two horIZontal ducts
fIGure 8.
Confined space should be provided with two permanent horizontal  
ducts, one commencing within 12 inches (300 mm) of top and one
commencing within 12 inches (300 mm) of bottom of enclosure. Horizontal
ducts should communicate directly with outdoors. See Figure 8.
Each duct opening should have a minimum free area of 1 square inch 
per 2,000 Btu/hr (1100 mm
2
per kW) of the aggregate input rating of all
appliances installed in the enclosure.
When ducts are used, they should be of the same cross sectional area 
as the free area of the openings to which they connect. The minimum 
dimension of rectangular air ducts should be not less than 3 inches. 
outdoor aIr throuGh two vertIcal ducts
The illustrations shown in this section of the manual are a reference for 
the openings that provide fresh air into confined spaces only.
Do not refer to these illustrations for the purpose of vent installation. 
See Installation of Vent System on pages 18-27 for complete venting 
installation instructions.
fIGure 9.
The confined space should be provided with two permanent vertical
ducts, one commencing within 12 inches (300 mm) of the top and
one commencing within 12 inches (300 mm) of the bottom of the
enclosure. The vertical ducts should communicate directly with the 
outdoors. See Figure 9.
Each duct opening should have a minimum free area of 1 square inch 
per 4,000 Btu/hr (550 mm
2
per kW) of the aggregate input rating of
all appliances installed in the enclosure. 
When ducts are used, they should be of the same cross sectional  
area as the free area of the openings to which they connect. The 
minimum dimension of rectangular air ducts should be not less than 
3 inches.
aIr froM other Indoor spaces
fIGure 9a.
The  confined  space  should  be  provided  with  two  permanent 
openings, one commencing within 12 inches (300 mm) of the top
and one commencing within 12 inches (300 mm) of the bottom of
the enclosure. See Figure 9A.
Each opening should communicate directly with an additional room(s)
of sufficient volume so that the combined volume of all spaces meets
the criteria for an Unconfined Space.
Each opening should have a minimum free area of 1 square inch per 
1,000 Btu/hr (1100 mm
2
per kW) of the aggregate input rating of all
appliances installed in the enclosure. Each opening should not be 
less than 100 square inches (645 cm
2
).