Hitachi RAC-25WSA RAC25WSA Benutzerhandbuch

Produktcode
RAC25WSA
Seite von 706
 
14-10
 
 
14.2.3  MONO SPLIT RAK-18/25/35PSA / RAC-18/25/35WSA, RAK-18/25/35PSAN / RAC-18/25/35WSAN , RAK-
18/25/35PSPA / RAC-18/25/35WSPA 
Disharge Procedure 
1.  Turn off the power of the indoor/outdoor unit and pull out the power supply plug. 
2.  After power is turned off, wait for 15 minutes or more. Then remove the electrical parts cover and apply soldering iron of 30 to 
75W at the positive and negative terminals of IPM, and discharge the charge voltage of the smoothing capacitor. 
 
Applicable models : RAK-18/25/35PSA / RAC-18/25/35WSA, RAK-18/25/35PSAN / RAC-18/25/35WSAN , RAK-18/25/35PSPA 
/ RAC-18/25/35WSPA
 
 
 
Do no use a soldering iron with transformer: If 
one is used, thermal fuse inside transformer 
will be blown. 
14.2.4  MONO SPLIT RAK-18/25/35PPA / RAC-18/25/35WPA, RAK-18/25/35/50PEA / RAC-18/25/35/50WEA , 
RAF-25/35PXA / RAC-25/35FXA RAF-50RPA / RAC-50FPA 
Disharge Procedure 
1.     Turn off the power of the indoor/outdoor unit and  pull out the power supply plug. 
2.     After power is turned off, wait for 10 minutes or more. Then remove the electrical parts cover and apply soldering iron of 30 to 
75W for 15 seconds or more to TAB05 and R001 terminals on the main P.W.B. as shown in the figure below. In order to 
discharge voltage in smoothing capacitor 
• 
Applicable models : RAK-18/25PPA / RAC-18/25WPA, RAK-
18/25PEA / RAC-18/25WEA 
• 
Applicable models : RAK-35PPA / RAC- 35WPA, RAK-
35PEA / RAC- 35WEA, RAF-25/35PXA / RAC-25/35FXA 
 
 
• 
Applicable models : RAK-50PEA / RAC-50WEA , RAF-50RPA 
/ RAC-50FPA
 
 
 
Do not use a soldering iron with transformer: Otherwise, 
thermal fuse inside transformer will be blown.
 
Lead wire 
Wire 
MAIN P.W.B 
SERVICE SWITCH 
HIC 
IPM 
MAIN P.W.B 
Lead wire 
TESTSWITCH 
Lead wire