Daikin FTXG50JV1BA Merkblatt

Seite von 1
fTxg
Heat pump
Series
available in 0.75, 1.0, 1.4 ton
Hot stArt
ComfortABle 
mode
IntellIgent 
eye
WaLL MounTed TYPe (HeaT PuMP) FTXg series
model name
Indoor Unit
ftXg25Jv1BA
ftXg35Jv1BA
ftXg50Jv1BA
outdoor Unit
rXg25K3v1B
rXg35K3v1B
rXg50K3v1B
Capacity
Cooling
rated (min - max)
Kw
2.5 (1.3~3.0)
3.5 (1.4~3.8)
5.0 (1.7~5.3)
Heating
rated (min - max)
Kw
3.4 (1.3~4.5)
4.0 (1.4~5.0)
5.8 (1.7~6.5)
power supply
1phase, 220-240v, 50Hz
running Current 
(220-230-240v, 50Hz)
Cooling
rated
A
3.2-3.0-2.9
5.1-4.8-4.6
7.2-6.9-6.6
Heating
A
4.4-4.2-4.1
5.6-5.3-5.1
7.4-7.1-6.8
power Consumption
Cooling
rated 
(min - max)
W
560 (350 - 820)
890 (360 - 1220)
1560 (450 - 1880)
Heating
W
780 (320 - 1320)
990 (320 - 1500)
1600 (520 - 2500)
Cop
Cooling
rated
W/W
4.46
3.93
3.21
Heating
W/W
4.36
4.04
3.63
Indoor Unit
ftXg25Jv1BA
ftXg35Jv1BA
ftXg50Jv1BA
front panel Colour
silver
Airflow rate
Cooling
m³/min
8.8
10.1
10.3
cfm
311
357
364
Heating
m³/min
9.6
10.8
11.4
cfm
339
389
402
fan speed
5 steps, quiet and Automatic
sound levels 
(H/m/l/sl)
Cooling
dB (A)
38 / 32 / 25 /22
42 / 34 / 26 / 23
44 / 40 / 35 / 32
Heating
39 / 34 / 28 / 25
42 / 36 / 29 / 26
44 / 40 / 35 / 32
dimensions (HxWxd)
mm
295 x 915 x 155
machine Weight
kg
11
outdoor Unit
rXg25K3v1B
rXg35K3v1B
rXg50K3v1B
Casing colour
Ivory White
Compressor
type
Hermetically sealed swing type
sound levels (H/sl)
Cooling
dB (A)
46/43
48/44
Heating
47/44
48/45
dimensions (HxWxd)
mm
550 x 765 x 285
735 x 825 x 300
machine Weight
kg
34
48
operation range
Cooling
°CdB
-10°C to 46°C
Heating
°CWB
-15°C to 20°C
max. piping length
m
20
30
max. Height difference
15
20
Measurement conditions:
1. Cooling capacity is based on: indoor temp. 27° CdB, 19° CWB; outdoor temp. 35° CdB; piping length 7.5 m. 
2. Heating capacity is based on: indoor temp. 20° CdB; outdoor temp. 7° CdB, 6° CWB; piping length 7.5 m.
3. sound levels are based on temperature conditions 1. and 2. above. these are anechoic conversion values. these values are normally somewhat higher during actual operation 
as a result of ambient conditions.