TE Connectivity Blade terminal Connector width: 6.3 mm Connector thickness: 0.8 mm 180 ° Insulated Blue 3-520107-2 1 pc 3-520107-2 Datenbogen

Produktcode
3-520107-2
Seite von 7
108-2043
Test Description
Requirem ent
Procedure
Heat Cycling (Current Cycling).
  W ire Size      Current (am peres)
    (AW G)         .110          Others   
        26                2               2
        24                4               4
        22                4               6
        20                6               8
        18                8              14
        16               10             20
        14               15             30
        12                –              40
        10                –              48
65°C m axim um  tem perature rise.
Ä Tem perature rise between 24 and
500 cycles shall not exceed 15°C
on any conductor.
UL 310.
Subject sam ples to 500 current
cycles of 45 m inutes ON and 15
m inutes OFF.
MECHANICAL
Pull Out (Crim p Tensile).
   W ire Size            Tensile
     (AW G)         (Lbs m inim um )      
        26                       4
        24                       6
        22                      10
        20                      16
Above values are less than
m axim um  withdrawal force. See
Figure 2.
        18                      20
        16                      30
        14                      60
        12                      70
        10                      80
UL 310.
Apply a direct and gradual pull at a
rate of 1 inch per m inute, 1 m inute
hold at specified load.
Secureness of Insulation
(Unassem bled).
No separation of the insulation from
the term inal body.
UL 310.
Subject unwired term inals to a 3
pound pull between the insulation
and term inal for 1 m inute.
Secureness of Insulation
(Assem bled).
No separation of the insulation from
the term inal body.
UL 310.
Subject wired term inals to a 6
pound pull between the insulation
and term inal for 1 m inute.
Engagem ent-Disengagem ent
(Engaging-Separating).
See Figure 2.
UL 310.
Engage and disengage term inals
and tabs 6 tim es.
ENVIRONMENTAL
Heat Age, 136°C.
Meet Dielectric W ithstanding
Voltage, Test Condition A; and
Secureness of Insulation
(assem bled and unassem bled).
UL 310.
Subject term inals to 136°C for 7
days.
Heat Age/Hum idity.
Meet Dielectric W ithstanding
Voltage, Test Condition A.
UL 310.
Subject unwired term inals to 100EC
for 7 days followed by 85%  RH at
30EC for 24 hours.
Figure 1 (end)
Rev D
3 of 5