Fluke Fluke 4325162 Benutzerhandbuch

Produktcode
4325162
Seite von 56
1625-2 
Users Manual 
30 
3.  Press "START TEST"-button and note result of R
E
 value.  
4.  Connect clip-on transformer. See Figure 9. 
 
edw018.eps 
Figure 9. Clip-on Transformer Connection 
5.  Turn central rotary switch to position " RE 3pole".  
6.  Press "START TEST" again. 
If the measured value R
E
 deviates from the R
E
 value determined without clip-on 
transformer by more than 5 %, adjust the clip-on transformation ratio (tr) correspondingly: 
)
(
)
(
mer
onTransfor
p
withoutcli
R
mer
ontransfor
withclip
R
trold
trnew
E
E
×
=
 
Example: 
Your clip-on transformer has a transformation ratio of tr = 1000:1. The measurement 
without clip-on transformer results in a value R
E
 = 0.983 
Ω
. With a clip-on transformer a 
value of R
E
 = 1.175 
Ω
 is measured.  
The deviation thus reads (1.175 - 0.983) 
Ω
 = + 0.192 
Ω
 and referring to R
E
 = 0.983 
Ω
 an 
error evolves as following: 
%
5
.
19
983
.
0
192
.
0
%
100
+
=
Ω
Ω
×
 
The new transformation ratio to be set calculates: 
1195
983
.
0
175
.
1
1000
=
×
=
trnew