Megger VDE-tester 1005-019 Datenbogen

Produktcode
1005-019
Seite von 3
PAT400 SERIES 
Portable Appliance Testers
SPECIFICATIONS
Electrical supply range
PAT410 and PAT450   
230 V ± 10% @ 50/60 Hz
Bond test (10 A and 25 A) (not PAT410) 
Open circuit voltage:   
9 V a.c. ± 10% ± 0.1 V  
 
   (Supply: 
230 
50Hz)
Earth bond resistance accuracy:  
 
 
 
±5% ±3 digits (0 to 0.49 Ω)
 
 
 
±5% ±5 digits 0.5 to .99 Ω)
Earth bond resistance resolution:  10 mΩ (0 to 1.99 Ω)
Display range: 
 
0 to 1.99 Ω
Continuity test (200 mA)
Continuity test voltage: 
4.0 V d.c. -0% +10% 
Continuity resistance accuracy: ±5% ±3 digits (0 to 0.49 Ω)
 
 
 
±5% ±5 digits 0.5 to .99 Ω)
Continuity resistance resolution:  10 mΩ (1 to 19.99 Ω)
Display range: 
 
0 to 19.99 Ω
Insulation test (250 V and 500 V)
Insulation resistance accuracy (230 V): 
 
 
 
±2% ±5 digits (0 to 19.99 MΩ)
 
 
 
±5% ±10 digits (20 to 99.99 MΩ)
Insulation resistance resolution: 0.01 MΩ 
Display range: 
0 to 99.99 MΩ
Substitute leakage test
Test voltage and frequency: 
40 V a.c. ±10% nominal mains    
   frequency
Leakage current accuracy: 
±5% ±5 digits
Leakage current resolution: 
0.01 mA 
Display range: 
 
0 to 19.99 mA
Differential leakage current
Test voltage and frequency: 
Nominal mains supply
Differential leakage current accuracy:  ±5% ±5 digits
Differential leakage current resolution:  0.01 mA
Display range: 
 
0 to 19.99 mA
Touch current test
Test voltage and frequency: 
Nominal mains supply
Touch current accuracy: 
±5% ±5 digits
Touch current resolution: 
0.01 mA
Display:   
 
0 to 10 mA 
Operational test
Test voltage and frequency: 
Nominal mains supply
VA accuracy: 
 
±5% ±10 digits (0 - 99 VA)
 
 
 
±5% ±50 digits (100 VA - 999 VA)
 
 
 
±5% ±100 digits (1000 VA - 3700 VA)
Resolution: 
 
1 VA (0 to 3700 VA)
Display range: 
 
0 to 3999 VA
Extension lead test
Tests performed: 
 
Bond, insulation and polarity
Polarity test voltage:   
12 V
Polarity checks: 
 
Lead OK
   Live 
neutral 
S/C
   Live 
neutral 
reversed
   Live/neutral 
O/C
 
PAT410 PAT450
SUPPLY  
230 V 
n
 
n
Supply measurement 
n
 
n
EARTH BOND/CONTINUITY   
200 mA 
n
 
n
10 A 
 
n
25 A 
 
n
Bond lead null 
n
 
n
INSULATION TEST  
 
250 V 
n
 
n
500 V 
n
 
n
ALTERNATIVE LEAKAGE TESTS
 
  
Substitute 
n
 
n
Differential 
n
 
n
Touch current 
n
 
n
OPERATION TEST 
  
VA Measurement 
n
 
n
EXTENSION LEAD TESTS  
Earth bond 
n
 
n
Insulation 
n
 
n
Polarity 
n
 
n
Portable RCD tests 
n
 
n
FLASH TEST  
1.5 kV and 3 kV 
  
n
OTHER FEATURES 
  
Low-profile light weight 
n
 
Auto test routine 
n
 
n
Manual testing 
n
 
n
Fuse check 
n
 
n
Colour display 
n
 
n
Configurable tests times 
n
 
n
Selectable pass limits 
n
 
n
Lead storage pouch 
n
 
n
10,000 record on-board storage 
n
 
n
Download to USB memory stick 
n
 
n
PowerSuite compatible 
n
 
n